B-44
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Phasor Measurement Unit Test Values (Read/Write Setting) (2 modules)
78AE
PMU 1 Test Function
0 to 1
---
1
F102
0 (Disabled)
78AF
PMU 1 Phase A Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78B1
PMU 1 Page A Voltage Test Angle
-180 to 180
°
0.05
F002
0
78B2
PMU 1 Phase B Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78B4
PMU 1 Phase B Voltage Test Angle
-180 to 180
°
0.05
F002
-12000
78B5
PMU 1 Phase C Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78B7
PMU 1 Phase C Voltage Test Angle
-180 to 180
°
0.05
F002
12000
78B8
PMU 1 Auxiliary Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78BA
PMU 1 Auxiliary Voltage Test Angle
-180 to 180
°
0.05
F002
0
78BB
PMU 1 Phase A Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
78BD
PMU 1 Phase A Current Test Angle
-180 to 180
°
0.05
F002
-1000
78BE
PMU 1 Phase B Current Test Magnitude
0 to 9.999
kA
0.001
F004
1000
78C0
PMU 1 Phase B Current Test Angle
-180 to 180
°
0.05
F002
-13000
78C1
PMU 1 Phase C Current Test Magnitude
0 to 9.999
kA
0.001
F003
1000
78C3
PMU 1 Phase C Current Test Angle
-180 to 180
°
0.05
F002
11000
78C4
PMU 1 Ground Current Test Magnitude
0 to 9.999
kA
0.001
F004
0
78C6
PMU 1 Ground Current Test Angle
-180 to 180
°
0.05
F002
0
78C7
PMU 1 Test Frequency
20 to 70
Hz
0.001
F003
60000
78C9
PMU 1 Test df/dt
-10 to 10
Hz/s
0.01
F002
0
78CA
...Repeated for PMU 2
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
0 to 2
---
1
F137
0 (Disabled)
7B61
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
7B6B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
7B75
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
7B7F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
7B80
User Programmable Pushbutton 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7B81
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
7B82
User Programmable Pushbutton 1 LED Operand
0 to 4294967295
---
1
F300
0
7B84
User Programmable Pushbutton 1 Autoreset Delay
0.2 to 600
s
0.1
F001
10
7B85
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
7B86
User Programmable Pushbutton 1 Local Lock Operand
0 to 4294967295
---
1
F300
0
7B88
User Programmable Pushbutton 1 Message Priority
0 to 2
---
1
F220
0 (Disabled)
7B89
User Programmable Pushbutton 1 Remote Lock Operand
0 to 4294967295
---
1
F300
0
7B8B
User Programmable Pushbutton 1 Reset Operand
0 to 4294967295
---
1
F300
0
7B8D
User Programmable Pushbutton 1 Set Operand
0 to 4294967295
---
1
F300
0
7B8F
User Programmable Pushbutton 1 Hold
0 to 10
s
0.1
F001
1
7B90
...Repeated for User Programmable Pushbutton 2
7BC0
...Repeated for User Programmable Pushbutton 3
7BF0
...Repeated for User Programmable Pushbutton 4
7C20
...Repeated for User Programmable Pushbutton 5
7C50
...Repeated for User Programmable Pushbutton 6
7C80
...Repeated for User Programmable Pushbutton 7
7CB0
...Repeated for User Programmable Pushbutton 8
7DE0
...Repeated for User Programmable Pushbutton 9
7D10
...Repeated for User Programmable Pushbutton 10
7D40
...Repeated for User Programmable Pushbutton 11
7D70
...Repeated for User Programmable Pushbutton 12
7DA0
...Repeated for User Programmable Pushbutton 13
7DD0
...Repeated for User Programmable Pushbutton 14
7E00
...Repeated for User Programmable Pushbutton 15
7E30
...Repeated for User Programmable Pushbutton 16
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...