5-194
C60 Breaker Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
The undervoltage delay setting defines the family of curves shown below.
(EQ 5.18)
where:
T
= operating time
D
= undervoltage delay setting (
D
= 0.00 operates instantaneously)
V
= secondary voltage applied to the relay
V
pickup
= pickup level
Figure 5–79: INVERSE TIME UNDERVOLTAGE CURVES
At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting.
T
D
1
V
V
pickup
------------------
–
----------------------------------
=
842788A1.CDR
% of voltage pickup
T
ime
(seconds)
NOTE
Содержание C60
Страница 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 423: ...GE Multilin C60 Breaker Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 28 ...
Страница 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Страница 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Страница 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 682: ...x C60 Breaker Protection System GE Multilin INDEX ...