Troubleshooting Position, Pressure, and Temperature Sensors
Actuator error alarm active
Handwheel or other travel
restriction in place.
The handwheel on the actuator
is not in neutral or is partially
engaged
1. Verify mounting and link-
age are correct.
2. Run Auto Tune.
3. Run Manual Tune.
4. Verify supply pressure.
N/A
Extreme valve sticking
Using ValVue Trend,
see if
the valve has friction
greater than 50% of the
spring range or
Observe the valve
and
see if the movement
jumps significantly with
a smooth
input signal.
Repair the valve when
possible.
N/A
Insufficient air supply
Using ValVue or another
HART
®
interface, verify
that
the air supply setting.
It must be set to 5 psi (.35
bar, 34.5 kPa) greater than
the spring final.
For double-acting actuator,
the air supply must be that
required to generate the
force to move the valve.
Increase the air supply per
the actuator requirements
N/A
Table 27 Troubleshooting Tuning (Continued)
Problem
Presumed Cause
Remedy
See Section
Содержание Baker Hughes Masoneilan SVI FF
Страница 12: ...This page intentionally left blank ...
Страница 72: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 108: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 230: ...This page intentionally left blank ...
Страница 250: ...This page intentionally left blank ...
Страница 262: ...This page intentionally left blank ...
Страница 263: ......