2-14
B90 Low Impedance Bus Differential System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.2.6 POWER SUPPLY
LOW RANGE
Nominal DC voltage:
24 to 48 V
Minimum DC voltage:
20 V
Maximum DC voltage:
60 V
Voltage loss hold-up:
20 ms duration at nominal
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
125 to 250 V
Minimum DC voltage:
88 V
Maximum DC voltage:
300 V
Nominal AC voltage:
100 to 240 V at 50/60 Hz
Minimum AC voltage:
88 V at 25 to 100 Hz
Maximum AC voltage:
265 V at 25 to 100 Hz
Voltage loss hold-up:
200 ms duration at nominal
ALL RANGES
Volt withstand:
2
Highest Nominal Voltage for 10 ms
Power consumption:
typical = 15 to 20 W/VA
maximum = 50 W/VA
contact factory for exact order code con-
sumption
INTERNAL FUSE
RATINGS
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
INTERRUPTING CAPACITY
AC:
100 000 A RMS symmetrical
DC:
10 000 A
2.2.7 OUTPUTS
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break (DC inductive, L/R = 40 ms):
Operate time:
< 4 ms
Contact material:
silver alloy
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A as per IEEE C37.90
Break (DC resistive as per IEC61810-1):
Operate time:
< 4 ms
Contact material:
silver alloy
Control:
separate operate and reset inputs
Control mode:
operate-dominant or reset-dominant
FORM-A VOLTAGE MONITOR
Applicable voltage:
approx. 15 to 250 V DC
Trickle current:
approx. 1 to 2.5 mA
FORM-A CURRENT MONITOR
Threshold current:
approx. 80 to 100 mA
FORM-C AND CRITICAL FAILURE RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
8 A
Break (DC inductive, L/R = 40 ms):
Operate time:
< 8 ms
Contact material:
silver alloy
FAST FORM-C RELAY
Make and carry:
0.1 A max. (resistive load)
Minimum load impedance:
Operate time:
< 0.6 ms
Internal Limiting Resistor: 100
, 2 W
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
VOLTAGE
CURRENT
24 V
6 A
48 V
1.6 A
125 V
0.4 A
250 V
0.2 A
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
INPUT
VOLTAGE
IMPEDANCE
2 W RESISTOR
1 W RESISTOR
250 V DC
20 K
50 K
120 V DC
5 K
2 K
48 V DC
2 K
2 K
24 V DC
2 K
2 K
Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load impedance.
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...