10-8
B90 Low Impedance Bus Differential System
GE Multilin
10.4 SLOPES AND HIGH SET THRESHOLD
10 APPLICATION OF SETTINGS
10
10.4.5 EXTERNAL FAULTS ON C-4
The following table presents the results of analysis of an external fault on circuit C-4 (C-4 is connected to the North bus; C-
3 and C-5 are connected to the South bus).
By comparing the secondary currents (column 3 in the table below) with the limits of linear operation for the CTs (column 4
in the Limits of Linear Operations of the CTs table shown earlier), it is concluded that none of the CTs will saturate due to
the AC currents during this fault.
Columns 6 and 7 of the following table summarize the DC saturation threat for the fault on C-4. CT-4, CT-6, CT-7, and CT-
8 may saturate due to the DC components and may generate a spurious differential signal for both the North and South bus
relays depending on the bus configuration. The saturation will not occur before 5.85 ms and will be detected by the Satura-
tion Detector.
10.4.6 EXTERNAL FAULTS ON C-5
The following table presents the results of analysis of an external fault on circuit C-5 (C-5 is connected to the North bus; C-
3 and C-4 are connected to the South bus).
By comparing the secondary currents (column 3 in the table below) with the limits of linear operation for the CTs (column 4
in the Limits of Linear Operations of the CTs table shown earlier), it is concluded that none of the CTs will saturate due to
the AC currents during this fault.
Columns 6 and 7 of the following table summarize the DC saturation threat for the fault on C-5. CT-4, CT-5, CT-7, and CT-
8 may saturate due to the DC components and may generate a spurious differential signal for both the North and South bus
relays depending on the bus configuration. The saturation will not occur before 4.83 ms and will be detected by the Satura-
tion Detector.
Table 10–7: EXTERNAL FAULT CALCULATIONS ON C-4
CT
I
FAULT
(KA)
I
FAULT
(A SEC)
T
DC
(MS)
AC
SATURATION
DC
SATURATION
T
SAT
(MS)
CT-1
0
0.00
N/A
No
No
N/A
CT-2
0
0.00
N/A
No
No
N/A
CT-3
6.0
25.00
5
No
No
N/A
CT-4
9.0
45.00
40
No
Yes
5.85
CT-6
3.0
15.00
40
No
Yes
35.25
CT-7, CT-8
9.0
37.50
40
No
Yes
9.40
Table 10–8: EXTERNAL FAULT CALCULATIONS ON C-5
CT
I
FAULT
(KA)
I
FAULT
(A SEC)
T
DC
(MS)
AC
SATURATION
DC
SATURATION
T
SAT
(MS)
CT-1
0
0.00
N/A
No
No
N/A
CT-2
0
0.00
N/A
No
No
N/A
CT-3
6.0
25.00
5
No
No
N/A
CT-4
5.0
25.00
30
No
Yes
15.19
CT-5
11.0
55.00
30
No
Yes
4.83
CT-7, CT-8
11.0
45.83
30
No
Yes
7.16
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...