CHAPTER 5: SETTINGS
INPUTS/OUTPUTS
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-259
5
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic equations used to customize the
device. Virtual outputs can also serve as virtual inputs to FlexLogic equations.
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the
COMMANDS
menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the
appropriate input signal is received.
If the
VIRTUAL INPUT x FUNCTION
is to “Disabled,” the input is forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled,” the input operates as shown on the logic diagram and generates output FlexLogic operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If
VIRTUAL INPUT x type
is “Self-Reset,” when the input signal
transits from off to on, the output operand is set to on for only one evaluation of the FlexLogic equations and then return to
off. If set to “Latched,” the virtual input sets the state of the output operand to the same state as the most recent received
input.
The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic equations. If the
operand is to be used anywhere other than internally in a FlexLogic equation, it likely needs to be lengthened in time. A
FlexLogic timer with a delayed reset can perform this function.
Figure 5-140: Virtual inputs logic
5.9.3 Contact outputs
5.9.3.1 Digital outputs
SETTINGS
INPUTS/OUTPUTS
CONTACT OUTPUTS
CONTACT OUTPUT H1
A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts
are supported.
VIRTUAL INPUT 1
EVENTS: Disabled
Range: Disabled, Enabled
CONTACT OUTPUT H1
CONTACT OUTPUT H1 ID
Cont Op 1
Range: up to 20 alphanumeric characters
OUTPUT H1 OPERATE:
Off
Range: FlexLogic operand
OUTPUT H1 SEAL-IN:
Off
Range: FlexLogic operand
CONTACT OUTPUT H1
EVENTS: Enabled
Range: Disabled, Enabled
Содержание b30
Страница 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 50: ...2 36 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 208: ...4 86 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 441: ...CHAPTER 5 SETTINGS CONTROL ELEMENTS B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL 5 233 5 Figure 5 123 Time out mode ...
Страница 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 514: ...6 28 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 528: ...7 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 554: ...9 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL OUTPUT LOGIC AND EXAMPLES CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 600: ...A 16 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 608: ...C 6 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...