B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
LOGIN
— This setting is applicable for Device authentication only. This setting allows a user to log in with a specific role, as
outlined here. For the Supervisor role, enable the “Supervisor Role” setting. Log out by right-clicking the device in EnerVista
and selecting the
Disconnect
option.
Whenever a new role is logged in, the user is prompted to enter a password. Passwords must obey the requirements
specified earlier in the chapter in the Password Requirements section.The UR device supports five roles. Roles have their
corresponding passwords, except the Observer role, which does not require a password. There are no time-outs for the
Administrator, Engineer, Operator, and Supervisor when logged in using the front panel; log out manually or use the
Command > Security
commands in the software.
The roles are defined as follows:
•
Administrator — Complete read/write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
•
Engineer — Complete read/write access to all settings and commands except configuring Security settings and
firmware upgrades. This role does not allow concurrent access.
•
Operator — The Operator has read/write access to all settings under the Commands menu/section. This role does not
exist offline.
•
Supervisor — This is only an approving role. This role’s authentication commits setting changes submitted by
Administrator or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not
approve changes after the fact. Only a Supervisor can set the Settings Lock and Firmware Lock in the Security
settings. This role also has the ability to forcefully log off any other role and clear the security event log. This role can
also be disabled, but only through a Supervisor authentication. When this role is disabled its permissions are assigned
to the Administrator role.
•
Observer — This role has read-only access to all B30 settings. This role allows unlimited concurrent access but it has
no download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel. When local authentication is used, no password is required for
this role. When RADIUS server authentication is used, a password is required.
Change local passwords
SETTINGS
PRODUCT SETUP
SECURITY
CHANGE LOCAL PASSWORDS
DEVICE
AUTHENTICATION: Yes
Range: Yes, No
FACTORY SERVICE
MODE: Disabled
Range: Enabled, Disabled
SESSION
SETTINGS
RESTORE DEFAULTS
SUPERVISORY
SYSLOG IP ADDRESS:
0.0.0.0
Range: 0.0.0.0, 255.255.255.255
SYSLOG PORT NUMBER:
514
Range: 1 to 65535
The Factory service role is not available. It is for factory use only.
The Local Access Denied message on the front panel can mean that you need to log in to the UR in order to
complete the action.
CHANGE LOCAL
PASSWORDS
LOGIN:
None
Range: 20 alphanumeric characters
Содержание b30
Страница 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 50: ...2 36 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 208: ...4 86 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 441: ...CHAPTER 5 SETTINGS CONTROL ELEMENTS B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL 5 233 5 Figure 5 123 Time out mode ...
Страница 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 514: ...6 28 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 528: ...7 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 554: ...9 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL OUTPUT LOGIC AND EXAMPLES CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 600: ...A 16 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 608: ...C 6 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...