120
•
Appendix C - DeviceNet™ to Modbus™ Gateway
ID Data
Type
Rule
1 Revision
UINT
1 Get
C.14.2.
Instance Attributes (Instance 1)
Attribute
ID
Name Range
Default
Value
Access
Rule
Modbus
Address
1 Starting
VOLT-2
10-80
30
Get/Set
40049
2 Current
Limit-2
100-
500
400 Get/Set
40050
3 Ramp
UP-2 1-90
10
Get/Set
40051
4 Ramp
DOWN-2
1-30
10
Get/Set
40052
5 Motor
Current-2
5-1400
105
Get/Set
40053
C.14.3.
Common Services
Implemented for
Service
Code
Class Level
Instance Level
Service Name
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set
Attribute
Single
C.15.
Slow SP & Saving Parameters Object (75
HEX –
1 Instance)
C.15.1.
Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data Value
Access
Rule
1 Revision
UINT
1 Get
C.15.2.
Instance Attributes (Instance 1)
Attribute
ID
Name Range
Default
Value
Access
Rule
Modbus
Address
1 Energy
Saving 0-10
10
Get/Set
40057
2
Slow Speed TRQ.
1-10
8
Get/Set
40058
3 Max_Slow_SP_Time
1-250
30
Get/Set
40059
C.15.3.
Common Services
Implemented for
Service
Code
Class Level
Instance Level
Service Name
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set
Attribute
Single
C.16.
Fault Settings Object (76
HEX –
1 Instance)
C.16.1.
Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data Value
Access
Rule
1 Revision
UINT
1 Get
C.16.2.
Instance Attributes (Instance 1)
Attribute
ID
Name Range
Default
Value
Access
Rule
Modbus
Address
1 Phase
Loss 0-1
0
Get/Set
40064
2 Phase
Sequence
0-1
0
Get/Set
40065
5 Auto_Reset
0-1
1
Get/Set
40066
6 Thermistor_Type
0-1
0
Get/Set
40067
7 Thermistor_Trip
0-100
(Tenth Kohm)
0 Get/Set
40068
8
Undercurrent RST
10-120 &
121 - OFF
121 Get/Set
40069