3.9 SP-## Special Functions
Parameter group related to special functions with regards
to Line Voltage, Reset Functions, Current Limit, Energy
Savings, Derating, and Accel/Decel Ramp Types.
SP-00 Fault Level
Option:
Function:
[0]
*
Off
Use this parameter to customize Fault levels. Use
[0] Off
with caution as it will ignore all Warnings
& Alarms for the chosen source.
[1]
Warning
[2]
Trip
[3]
Trip Lock
Failure
Alarm
Off
Warning
Trip
Trip Lock
10 V low
1
X
D
24 V low
47
X
D
1.8 V supply low
48
X
D
Voltage limit
64
X
D
Earth fault during ramping
14
D
X
Earth fault 2 during cont. operation
45
D
X
Torque Limit
12
X
D
Over Current
13
X
D
Short Circuit
16
X
D
Heatsink temperature
29
X
D
Heatsink sensor
39
X
D
Control card temperature
65
X
D
Power card temperature
69
1)
X
D
Heatsink temperature
1)
244
X
D
Heatsink sensor
1)
245
X
D
Power card temperature
1)
247
Table 3.16 Table for Selection of Choice of Action when Selected Alarm Appears
D = Default setting
x = possible selection
1) Only drives 125 HP and above. All others is just a warning.