3.19 LC-## Logic Controller
Parameter group related to programming the drive's built-
in Logic Controller. The Logic Controller consists of a series
of user defined actions (see
that are executed when the corresponding user-defined
events are met.
3.19.1 LC-0# LC Settings
Parameters to configure the activation, deactivations and
reset of the Logic Controller (LC).
LC-00 Logic Controller Mode
Option:
Function:
[0]
*
Off
Disables the Logic Controller.
[1]
On
Enables the Logic Controller.
LC-01 Start Event
Select the boolean (TRUE or FALSE) input to activate Logic
Controller.
Option:
Function:
[0]
*
False
Select the boolean (TRUE or FALSE)
input to activate Logic Controller.
Enters the fixed value - FALSE
[1]
True
Enters the fixed value - TRUE.
[2]
Running
The motor is running.
[3]
In range
The motor is running within the
programmed current and speed
[4]
On reference
The motor is running on reference.
[5]
Torque limit
The torque limit, set in
or
, has been exceeded.
[6]
Current Limit
The motor current limit, set in
, has been
exceeded.
[7]
Out of current
range
The motor current is outside the
range set in
.
[8]
Below I low
The motor current is lower than set
in
[9]
Above I high
The motor current is higher than set
in
[10]
Out of speed range The speed is outside the range set in
and
[11]
Below speed low
The output speed is lower than the
[12]
Above speed high
The output speed is higher than the
LC-01 Start Event
Select the boolean (TRUE or FALSE) input to activate Logic
Controller.
Option:
Function:
[13]
Out of feedb. range The feedback is outside the range set
in
.
[14]
Below feedb. low
The feedback is below the limit set in
.
[15]
Above feedb. high
The feedback is above the limit set in
.
[16]
Thermal warning
The thermal warning turns on when
the temperature exceeds the limit in
the motor, the frequency converter,
the brake resistor or the thermistor.
[17]
Line voltage out of
range
The mains voltage is outside the
specified voltage range.
[18]
Reversing
The output is high when the
frequency converter is running
counter clockwise (the logical product
of the status bits “running” AND
“reverse”).
[19]
Warning
A warning is active.
[20]
Alarm (trip)
A (trip) alarm is active.
[21]
Alarm (trip lock)
A (Trip lock) alarm is active.
[22]
Comparator 0
Use the result of comparator 0.
[23]
Comparator 1
Use the result of comparator 1.
[24]
Comparator 2
Use the result of comparator 2.
[25]
Comparator 3
Use the result of comparator 3.
[26]
Logic rule 0
Use the result of logic rule 0.
[27]
Logic rule 1
Use the result of logic rule 1.
[28]
Logic rule 2
Use the result of logic rule 2.
[29]
Logic rule 3
Use the result of logic rule 3.
[33]
Digital input DI18
Use the result of digital input 18.
[34]
Digital input DI19
Use the result of digital input 19.
[35]
Digital input DI27
Use the result of digital input 27.
[36]
Digital input DI29
Use the result of digital input 29.
[37]
Digital input DI32
Use the result of digital input 32.
[38]
Digital input DI33
Use the result of digital input 33.
[39]
Start command
A start command is issued.
[40]
Drive stopped
A stop command (Jog, Stop, Qstop,
Coast) is issued – and not from the
Logic Controller itself.
[41]
Reset Trip
A reset is issued
[42]
Auto-reset Trip
An Auto reset is performed.
[43]
Ok key
[OK] is pressed.
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
119