6.2.8 AN-## Analog In / Out
Par. No. # Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion
index
Type
AN-0#
AN-00
Live Zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
AN-01
Live Zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
AN-02
Fire Mode Live Zero Timeout Function
[0] Off
All set-ups
TRUE
-
Uint8
AN-1#
AN-10
Terminal 53 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
AN-11
Terminal 53 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
AN-12
Terminal 53 Low Current
4.00 mA
All set-ups
TRUE
-5
Int16
AN-13
Terminal 53 High Current
20.00 mA
All set-ups
TRUE
-5
Int16
AN-14
Terminal 53 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
AN-15
Terminal 53 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
AN-16
Terminal 53 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
AN-17
Terminal 53 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
AN-2#
AN-20
Terminal 54 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
AN-21
Terminal 54 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
AN-22
Terminal 54 Low Current
4.00 mA
All set-ups
TRUE
-5
Int16
AN-23
Terminal 54 High Current
20.00 mA
All set-ups
TRUE
-5
Int16
AN-24
Terminal 54 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
AN-25
Terminal 54 High Ref./Feedb. Value
100.000 N/A
All set-ups
TRUE
-3
Int32
AN-26
Terminal 54 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
AN-27
Terminal 54 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
AN-3#
AN-30
Terminal X30/11 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
AN-31
Terminal X30/11 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
AN-34
Term. X30/11 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
AN-35
Term. X30/11 High Ref./Feedb. Value
100.000 N/A
All set-ups
TRUE
-3
Int32
AN-36
Term. X30/11 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
AN-37
Term. X30/11 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
AN-4#
AN-40
Terminal X30/12 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
AN-41
Terminal X30/12 High Voltage
10.00 V
All set-ups
TRUE
-2
Int16
AN-44
Term. X30/12 Low Ref./Feedb. Value
0.000 N/A
All set-ups
TRUE
-3
Int32
AN-45
Term. X30/12 High Ref./Feedb. Value
100.000 N/A
All set-ups
TRUE
-3
Int32
AN-46
Term. X30/12 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
AN-47
Term. X30/12 Live Zero
[1] Enabled
All set-ups
TRUE
-
Uint8
AN-5#
AN-50
Terminal 42 Output
null
All set-ups
TRUE
-
Uint8
AN-51
Terminal 42 Output Min Scale
0.00 %
All set-ups
TRUE
-2
Int16
AN-52
Terminal 42 Output Max Scale
100.00 %
All set-ups
TRUE
-2
Int16
AN-53
Terminal 42 Output Bus Control
0.00 %
All set-ups
TRUE
-2
N2
AN-54
Terminal 42 Output Timeout Preset
0.00 %
1 set-up
TRUE
-2
Uint16
AN-6#
AN-60
Terminal X30/8 Output
[0] No operation
All set-ups
TRUE
-
Uint8
AN-61
Terminal X30/8 Min. Scale
0.00 %
All set-ups
TRUE
-2
Int16
AN-62
Terminal X30/8 Max. Scale
100.00 %
All set-ups
TRUE
-2
Int16
AN-63
Terminal X30/8 Output Bus Control
0.00 %
All set-ups
TRUE
-2
N2
AN-64
Terminal X30/8 Output Timeout Preset
0.00 %
1 set-up
TRUE
-2
Uint16
How to Program
AF-600 FP High Power Operating Instructions