Troubleshooting:
Ambient temperature too high.
Too long motor cable.
Incorrect clearance above and below the drive.
Dirty heatsink.
Blocked air flow around the drive.
Damaged heatsink fan.
For the 4x, 5x, and 6x unit size Drives, this alarm is based
on the temperature measured by the heatsink sensor
mounted inside the IGBT modules. For the 6x unit size
drives, this alarm can also be caused by the thermal sensor
in the Rectifier module.
Troubleshooting:
Check fan resistance.
Check soft charge fuses.
IGBT thermal sensor.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase
U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the
motor is missing.
Turn off the frequency converter and check motor phase
W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period. Let unit cool to operating temperature.
WARNING/ALARM 34, Network communication fault
The network on the communication option card is not
working.
WARNING/ALARM 35, Out of frequency range:
This warning is active if the output frequency has reached
the high limit (set in par. H-73) or low limit (set in par.
H-72).
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and
SP-10 Line failure
is NOT
set to OFF. Check the fuses to the frequency converter
ALARM 38, Internal fault
It may be necessary to contact your GE supplier. Some
typical alarm messages:
0
Serial port cannot be initialized. Serious hardware
failure
256-258 Power EEPROM data is defect or too old
512
Control board EEPROM data is defect or too old
513
Communication time out reading EEPROM data
514
Communication time out reading EEPROM data
515
Application Orientated Control cannot recognize the
EEPROM data
516
Cannot write to the EEPROM because a write
command is on progress
517
Write command is under time out
518
Failure in the EEPROM
519
Missing or invalid Barcode data in EEPROM
783
Parameter value outside of min/max limits
1024-
1279
A can-telegram that has to be sent, couldn't be sent
1281
Digital Signal Processor flash timeout
1282
Power micro software version mismatch
1283
Power EEPROM data version mismatch
1284
Cannot read Digital Signal Processor software version
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1302
Option SW in slot C1 is too old
1315
Option SW in slot A is not supported (not allowed)
1316
Option SW in slot B is not supported (not allowed)
1318
Option SW in slot C1 is not supported (not allowed)
1379
Option A did not respond when calculating Platform
Version.
1380
Option B did not respond when calculating Platform
Version.
1536
An exception in the Application Orientated Control is
registered. Debug information written in keypad
1792
DSP watchdog is active. Debugging of power part
data Motor Orientated Control data not transferred
correctly
2049
Power data restarted
2064-20
72
H081x: option in slot x has restarted
2080-20
88
H082x: option in slot x has issued a powerup-wait
2096-21
04
H083x: option in slot x has issued a legal powerup-
wait
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missing io_statepage from power unit
2324
Power card configuration is determined to be
incorrect at power up
2330
Power size information between the power cards does
not match
Warnings and Alarms
AF-600 FP High Power Operating Instructions
131
8
8
Содержание AF-600 FP Series
Страница 44: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 43 4 4...
Страница 45: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 44 4 4...
Страница 46: ...Please note airflow directions Mechanical Installation AF 600 FP High Power Operating Instructions 45 4 4...