47
Advent Commercial Fire System
Partition/Area Text Displayed on Touchpads and
Spoken Over Speakers
17125
(System)
(Default = on) If on, partition/area text (49004) will be displayed
on touchpads
and
spoken over speakers. If off, partition/area text
will only be displayed on touchpads.
To turn Partition/Area Text Displayed on
Touchpads and Spoken Over Speakers On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Enable Daylight Savings
17070
(System)
(Default = on) This setting allows you to select whether or not the
panel adjusts to daylight savings time. If on, the clock makes
daylight savings adjustments at 2:00 AM on the first Sunday in
April and the last Sunday in October. The time will spring ahead
from 01:59 to 03:00 or fall back from 01:59 to 01:00.
To turn Daylight Savings t On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Print System Events
17099
(System)
(Default = on) This setting allows you to select whether or not to
print system events.
Note
This setting only enables the printing of
system
events.
See
Print Partition/Area Events
setting (xx091) on
page 22 to enable partition/area event printing.
To turn Print System Events On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Print Line Feed after Carriage Return
17097
(System)
(Default = on) This setting allows you to select whether or not to
print a line feed after a carriage return. This will tell the printer to
print a line feed, creating an extra blank line.
Some printers have an auto line feed setting. If the printer adds its
own extra line feed, disable this setting so that it doesn’t print
extra blank lines. Check the printer manual for details.
To turn Print Line Feed after Carriage Return On/
Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Printer Supports Epson ESC/P Protocol
17124
(System)
(Default = on) Turn this setting on if the printer attached to the
panel supports ESC/P protocol. Check the printer manual for
details.
To turn Epson ESC/P Protocol On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Hours to Delay Before Reporting AC Failure
17041
(System)
(Default = 6 hours) This setting allows you to select the hours to
delay (in addition to random 0–30 minute delay) before the panel
reports AC power failure to the central station.
To set Hours to Delay Before Reporting AC
Failure:
Once in program mode enter the item number. Enter the desired
delay (0–36) and press
ƒ
.
Low Battery Trip Voltage
17037
(System)
(Default = 180 [10.6V]) This setting allows you to specify the
backup battery voltage at which low battery trouble is generated
(set in 1/17 volt units).
To set Low Battery Trip Voltage:
Once in program mode enter the item number. Enter the desired
voltage (172–188 [10.1–11.1V]) and press
ƒ
.
Battery Restored Voltage
17038
(System)
(Default = 196 [11.6V]) This setting allows you to set the voltage
at which a low battery trouble restoral is generated (set in 1/17
volt units).
To set Battery Restoral Voltage:
Once in program mode enter the item number. Enter the desired
voltage (188–204 [11.1–12.0V]) and press
ƒ
.
Battery Voltage Shutdown is Started
17039
(System)
(Default = 159 [9.4V
]
) This setting allows you to set the backup
battery voltage at which a system shutdown (during an AC power
failure) is started (set in 1/17 volt units).
To set Battery Voltage Shutdown is Started:
Once in program mode enter the item number. Enter the desired
voltage (151–167 [8.9–9.8V]) and press
ƒ
.