17
Advent Commercial Fire System
Special Programming Settings
Partitions/General Partition Settings
Clear Panel Memory
50002
(Default = n/a) It is recommended that you clear memory on all
newly installed panels before programming. Clearing memory
deletes setup values and resets all values to factory defaults.
To Clear Panel Memory:
1.
Enter program mode.
2.
Enter the installer code.
3.
Enter item number 50002.
4.
Press 99 and then
ƒ
. Wait about a minute until touchpads
return to their default displays.
Note
Since all programming information is contained in mem-
ory, clearing memory deletes all existing programming
information except dealer values (if any).
Reviewing (List) Settings
00000
(Default = n/a) An easy way of listing all programming settings
and their values is provided. You can list
all
settings, or settings
starting at a selected item number.
To list
all
Settings:
1.
Once in program mode enter the item number (00000).
2.
Press
ƒ
to start listing settings from the beginning
or
enter the item number you wish to start at and press
ƒ
.
Touchpads will flash each of the item numbers and values
(if not protected by dealer password).
3.
Press
‚
at any time to exit this menu.
Note
Displayed setting values may be viewed but not changed
using this procedure.
Partitions Act As Areas
17127
(Partitions-General Partition Settings)
(Default = off) Choose whether or not to treat partitions as areas.
If treated as areas:
Zones, touchpads, schedules, programming options, etc.,
belong to areas instead of partitions.
Users may “jump” from one area to another area using an
alphanumeric touchpad.
The word “partition” will be changed to “area” wherever
it is spoken, displayed, or printed.
To turn Areas On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Touchpad Redirect Reset Time
17035
(Partitions-General Partition)
(Default = 10 seconds) This setting allows you to select the length
(in seconds) of inactivity (no menu activity) before a “jumped”
touchpad returns to its assigned area.
To set Touchpad Redirect Reset Time:
1.
Once in program mode enter the item number.
2.
Enter the desired length (5–60) and press
ƒ
.
Global Account Reporting
17093
(Partitions-General Partition)
(Default = off) The setting enables the panel to report events as a
system.
When set to on:
The panel will use system account and area numbers when
reporting events.
The panel will only perform one automatic phone test (not
one for each partition/area).
To turn Global Account Reporting On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Partitions Enabled
xx068
(Partitions-General Partition Settings)
(Defaults = Partition/Area 1 - on, all others off) Choose whether
or not to enable the partition/area. Partition/Area 1 is always
enabled.
To turn a Partition/Area On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.