![GE 90.017.102 Скачать руководство пользователя страница 122](http://html.mh-extra.com/html/ge/90-017-102/90-017-102_instruction-manual_131799122.webp)
GEK-106426B
MIB High Impedance Bus Differntial Relay
8-7
8 RELAY COMMISSIONING
8.7 COMMUNICATIONS
8
8.7COMMUNICATIONS
The communication test checks that the 2 communications ports (the front RS232 and the rear RS485) work properly. To
perform this test is necessary to establish the connection between the PC and the relay (refer to figure 3-10). If the front
port is used, a straight through cable is needed. If the rear RS485 port is used, an RS485/RS232 converter is needed. GE
Multilin offers DAC300, F485 or RS232/485 converters.
The communications parameters that have to be set in the computer should match the relay communication settings.
The factory default settings for the MIB relay are
Using the ENERVISTA MII SETUP program, communicate with the relay and in the Status window check that the
communications are not lost at any time. Perform this test on both communications ports.
COMMUNICATIONS
NAME
VALUE
UNITS
RANGE
Slave Address
1
1 - 255
Communication Port
COM1
COM1 – COM*
Baud Rate
9.600
Bauds
300 – 19 200
Parity
NONE
NONE – ODD - EVEN
Control type
No control type
No control type, Modem
connection, MODBUS/TCP
Start up mode
File Mode
Communicate with relay –
File mode
Содержание 90.017.102
Страница 19: ...1 14 MIB High Impedance Bus Differntial Relay GEK 106426B 1 4 USING THE KEYPAD AND DISPLAY 1 GETTING STARTED 1 ...
Страница 103: ...6 8 MIB High Impedance Bus Differntial Relay GEK 106426B 6 2 OUTPUTS AND LEDS CONFIGURATION 6 I 0 CONFIGURATION 6 ...
Страница 115: ...7 12 MIB High Impedance Bus Differntial Relay GEK 106426B 7 4 OPERATIONS 7 KEYPAD AND DISPLAY 7 ...
Страница 135: ...8 20 MIB High Impedance Bus Differntial Relay GEK 106426B 8 17 ADVANCED SETTINGS 8 RELAY COMMISSIONING 8 ...
Страница 162: ...GEK 106426B MIB High Impedance Bus Differntial Relay A 23 APPENDIX A A 8 USED FORMATS A ...
Страница 163: ...A 24 MIB High Impedance Bus Differntial Relay GEK 106426B A 8 USED FORMATS APPENDIXA A ...