1-6
735/737 Feeder Protection Relay
GE Power Management
1.3 SPECIFICATIONS
1 INTRODUCTION
1
1.3 SPECIFICATIONS
1.3.1 PROTECTION
PHASE TIME OVERCURRENT (51)
Pickup level:
LO: 20 to 100% of CT rating or OFF
HI: 110 to 220% of CT rating or OFF
Curve Types:
ANSI, IAC, IEC/BS142
Curve shapes:
definite time, moderately inverse, normal, inverse, very inverse, extremely inverse.
See time/overcurrent curves; curves apply up to 20 x pickup or 20 x CT, whichever is less.
Time multiplier:
10 curves: #1 to #10 for each shape
4 shift multipliers: 0.5, 0.8, 1, 1.1
Definite time:
100 ms to 1 sec. in steps of 100 ms.
Reset:
Time reset to zero each time current level falls below pickup threshold
Accuracy:
Level: ±3% of setting
Time: greater of ±3% or ±20ms at >150% of pickup
PHASE INSTANTANEOUS OVERCURRENT (50)
Pickup level:
4, 5, 6, 8, 10, 12, 14, 16, 20
×
CT or OFF
Accuracy:
Level: ±3% of setting
Time: 35ms maximum at
>
150% of pickup setting
GROUND TIME OVERCURRENT (51G/51N)
Pickup level:
LO: 15 to 55% of CT rating in steps of 5% or OFF
HI: 60 to 100% of CT rating in steps of 5% or OFF
Curve Types:
ANSI, IAC, IEC/BS142
Curve shapes:
definite time, moderately inverse, normal, inverse, very inverse, extremely inverse.
See time/overcurrent curves; curves apply up to 20
×
pickup or 20
×
sensor, whichever is less.
Time multiplier:
10 curves: #1 to #10 for each shape
4 shift multipliers: 0.5, 0.8, 1, 1.1
Definite time:
100 ms to 1 sec. in steps of 100 ms
Reset:
Time reset to zero each time current level falls below pickup
Accuracy:
Level: ±3% of setting
Time: greater of ±3% or ±20ms at
>
150% of pickup
GROUND INSTANTANEOUS OVERCURRENT (50G/50N)
Pickup level:
0.1, 0.2, 0.4, 0.8, 1, 2, 4, 8, 16,
×
CT or OFF
Accuracy:
Level: ±3% of setting
Time: 35ms maximum at
>
150% of pickup setting
1.3.2 INPUTS
CURRENT INPUTS
Withstand Phase/Ground CTs:4 times rated current: continuous
20 times rated current: 5 second
40 times rated current: 2 second
Sensing:
True RMS; 16 samples/cycle
Secondary:
1 A or 5 A (must be specified with order)
Accuracy:
greater of 3% of CT primary or 3% of displayed
Drift:
No greater than 0.5% over 10 years
CT BURDEN
1 Amp inputs:
0.02 VA at 1 A; 0.2 VA at 5 A; 10 VA at 20 A
5 Amp inputs:
0.02 VA at 5 A; 0.2 VA at 20 A; 10 VA at 100 A
Conversion range:
0 to 20 times CT primary
Frequency response:
48 to 300 Hz ± 3 dB
Содержание 735
Страница 10: ......
Страница 12: ......
Страница 16: ...iv 735 737 Feeder Protection Relay GE Power Management TABLE OF CONTENTS ...
Страница 46: ...3 18 735 737 Feeder Protection Relay GE Power Management 3 6 SETUP EXAMPLE 3 SETUP AND OPERATION 3 ...
Страница 90: ...5 28 735 737 Feeder Protection Relay GE Power Management 5 5 IEC CURVES 5 OVERCURRENT CURVES 5 ...
Страница 92: ...6 2 735 737 Feeder Protection Relay GE Power Management 6 1 PROCEDURES 6 TESTING 6 Figure 6 1 TEST SETUP ...
Страница 98: ...6 8 735 737 Feeder Protection Relay GE Power Management 6 2 TEST RECORDS 6 TESTING 6 ...
Страница 100: ...7 2 735 737 Feeder Protection Relay GE Power Management 7 1 SETTINGS TABLE 7 COMMISSIONING 7 ...
Страница 108: ...iv 735 737 Feeder Protection Relay GE Power Management INDEX ...
Страница 109: ...GE Power Management 735 737 Feeder Protection Relay NOTES ...