GE Power Management
735/737 Feeder Protection Relay
4-11
4 MODBUS COMMUNICATIONS
4.3 MEMORY MAP
4
SYSTEM
CONFIG
002A
Phase Pickup dial setting
1 to 19
1
dial
F108
---
002B
Phase Curve Shape dial setting
1 to 10
1
dial
F107
---
002C
Phase Time Multiplier dial setting
1 to 10
1
dial
F112
---
002D
Phase Instantaneous dial setting
1 to 10
1
dial
F109
---
002E
Ground Pickup dial setting
1 to 19
1
dial
F110
---
002F
Ground Curve Shape dial setting
1 to 10
1
dial
F107
---
0030
Ground Time Multiplier dial setting
1 to 10
1
dial
F112
---
0031
Ground Instantaneous dial setting
1 to 10
1
dial
F111
---
0032
Comm DIP switch setting
---
---
---
F102
---
0033
Curve shift switch setting
---
---
---
F114
---
0034
Reset switch status
0-1
1
1=on
F1
---
0035
Not used
---
---
---
---
---
↓
↓
↓
↓
↓
↓
↓
004F
Not used
---
---
---
---
---
SETPOINTS
DIAL
SETTINGS FOR
SIMULATION
AND TEST I/O
0050
Phase Pickup dial (Remote)
1 to 19
1
dial
F108
0
0051
Phase Curve Shape dial (Remote)
1 to 5
1
dial
F104
0
0052
Phase Time Multiplier dial (Remote)
1 to 10
1
dial
F112
0
0053
Phase Instantaneous dial (Remote)
1 to 10
1
dial
F109
0
0054
Ground Pickup dial (Remote)
1 to 19
1
dial
F110
0
0055
Ground Curve Shape dial (Remote)
1 to 5
1
dial
F104
0
0056
Ground Time Multiplier dial (Remote)
1 to 10
1
dial
F112
0
0057
Ground Instantaneous dial (Remote)
1 to 10
1
dial
F111
0
0058
Phase A current (Simulation)
0 to 2000
1
% CT
F1
0
0059
Phase B current (Simulation)
0 to 2000
1
% CT
F1
0
005A
Phase C current (Simulation)
0 to 2000
1
% CT
F1
0
005B
Ground current (Simulation)
0 to 2000
1
% CT
F1
0
005C
Output relays (Test - I/O)
Bits
---
---
F103
0
005D
LED (Test - I/O)
Bits
---
---
F105
0
005E
Bargraph (Test - I/O)
Bits
---
---
F106
0
005F
Curve shift switch
Bits
---
---
F114
0
CUSTOM
SCHEME
0060
Curve Shape
0 to 2
1
---
F116
0
0061
Block Instantaneous
0 to 180
1
0=OFF
F117
OFF
0062
Aux Trip Relay
0 to 2
1
---
F118
0
COMMANDS
0063
Reset
0 to 1
1
1=reset
F1
0
0064
Clear Last Trips
0 to 1
1
1=clear
F1
0
0065
Not used
---
---
---
---
---
↓
↓
↓
↓
↓
↓
↓
006F
Not used
---
---
---
---
---
Table 4–1: 735/737 MODBUS MEMORY MAP (Sheet 2 of 2)
GROUP
ADDR
DESCRIPTION
RANGE
STEP
UNITS
FOR-
MAT
FACTORY
DEFAULT
Содержание 735
Страница 10: ......
Страница 12: ......
Страница 16: ...iv 735 737 Feeder Protection Relay GE Power Management TABLE OF CONTENTS ...
Страница 46: ...3 18 735 737 Feeder Protection Relay GE Power Management 3 6 SETUP EXAMPLE 3 SETUP AND OPERATION 3 ...
Страница 90: ...5 28 735 737 Feeder Protection Relay GE Power Management 5 5 IEC CURVES 5 OVERCURRENT CURVES 5 ...
Страница 92: ...6 2 735 737 Feeder Protection Relay GE Power Management 6 1 PROCEDURES 6 TESTING 6 Figure 6 1 TEST SETUP ...
Страница 98: ...6 8 735 737 Feeder Protection Relay GE Power Management 6 2 TEST RECORDS 6 TESTING 6 ...
Страница 100: ...7 2 735 737 Feeder Protection Relay GE Power Management 7 1 SETTINGS TABLE 7 COMMISSIONING 7 ...
Страница 108: ...iv 735 737 Feeder Protection Relay GE Power Management INDEX ...
Страница 109: ...GE Power Management 735 737 Feeder Protection Relay NOTES ...