GE Power Management
735/737 Feeder Protection Relay
4-7
4 MODBUS COMMUNICATIONS
4.2 SUPPORTED MODBUS FUNCTIONS
4
4.2.5 FUNCTION CODE 06: STORE SINGLE SETPOINT
Modbus Implementation: Preset Single Register
735/737 Implementation: Store Single Setpoint
This command allows the master to store a single setpoint into the memory of a slave device. The slave device response to
this function code is to echo the entire master transmission. Note that broadcast mode is not allowed with this function
code. When a broadcast transmission is sent by the master (that is, SLAVE ADDRESS = 0) the message will be ignored.
Message Format and Example:
Request slave 11 to store the value 039E in setpoint address 0049. After the transmission in this example is complete, set-
points address 0049 will contain the value 039E.
4.2.6 FUNCTION CODE 07: READ STATUS
Modbus Implementation: Read Exception Status
735/737 Implementation: Read General Status
This is a function used to quickly read the status of a selected relay. A short message length allows for rapid reading of sta-
tus. The status byte returned is the lower 8 bits of the relay status register defined in the memory map. Note that broadcast
mode is not allowed with this function code. The master transmission will be ignored by all slaves if broadcast mode is used
with this function code.
Message Format and Example:
Request status from slave 11. The status is stored in actual values memory map location 0014H. Assume the value is
01101101b.
MASTER TRANSMISSION:
BYTES
EXAMPLE / DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 11
FUNCTION CODE
1
06
store single setpoint
DATA STARTING ADDRESS
2
00 49
setpoint address 0049h
DATA
2
03 9E
data for address 0049h
CRC
2
?? ??
CRC calculated by the master
SLAVE RESPONSE:
BYTES
EXAMPLE / DESCRIPTION
SLAVE ADDRESS
1
11
response message from slave 11
FUNCTION CODE
1
06
store single setpoint
DATA STARTING ADDRESS
2
00 49
setpoint address 0049h
DATA
2
03 9E
data stored in 0049h
CRC
2
?? ??
CRC calculated by the slave
MASTER TRANSMISSION:
BYTES
EXAMPLE / DESCRIPTION
SLAVE ADDRESS
1
11
message for slave 11
FUNCTION CODE
1
07
read device status
CRC
2
?? ??
CRC calculated by the master
SLAVE RESPONSE:
BYTES
EXAMPLE / DESCRIPTION
SLAVE ADDRESS
1
11
response message from slave 11
FUNCTION CODE
1
07
read device status
CODE VALUE
1
6D
status = 001101101 (binary)
CRC
2
?? ??
CRC calculated by the slave
Содержание 735
Страница 10: ......
Страница 12: ......
Страница 16: ...iv 735 737 Feeder Protection Relay GE Power Management TABLE OF CONTENTS ...
Страница 46: ...3 18 735 737 Feeder Protection Relay GE Power Management 3 6 SETUP EXAMPLE 3 SETUP AND OPERATION 3 ...
Страница 90: ...5 28 735 737 Feeder Protection Relay GE Power Management 5 5 IEC CURVES 5 OVERCURRENT CURVES 5 ...
Страница 92: ...6 2 735 737 Feeder Protection Relay GE Power Management 6 1 PROCEDURES 6 TESTING 6 Figure 6 1 TEST SETUP ...
Страница 98: ...6 8 735 737 Feeder Protection Relay GE Power Management 6 2 TEST RECORDS 6 TESTING 6 ...
Страница 100: ...7 2 735 737 Feeder Protection Relay GE Power Management 7 1 SETTINGS TABLE 7 COMMISSIONING 7 ...
Страница 108: ...iv 735 737 Feeder Protection Relay GE Power Management INDEX ...
Страница 109: ...GE Power Management 735 737 Feeder Protection Relay NOTES ...