GE Power Management
735/737 Feeder Protection Relay
3-17
3 SETUP AND OPERATION
3.6 SETUP EXAMPLE
3
Slave address: 10
Baud rate: 9600
For a baud rate of 9600, 2=on, 1=off. Choose the combination of numbers that adds up to the required slave address: 10 =
2 (4=on) + 8 (6=on), (3=off, 5=off, 7=off). Disable communications test mode for normal operations (Test 8=off). The switch
settings are:
SWITCH
POSITION
SETTING
1
OFF
9600 baud
2
ON
3
OFF
Address 10
4
ON
5
OFF
6
ON
7
OFF
8
OFF
Test OFF