735/737 Feeder Protection Relay
3-7
3 SETUP AND OPERATION
3.3 INDICATORS
3
d) GROUND INSTANTANEOUS TRIP
When the ground (neutral) current exceeds the GROUND INSTANTANEOUS setting, the relay will trip and this indicator will
be set to indicate ground instantaneous trip.
3.3.3 PHASE CURRENT INDICATOR [12]
Maximum RMS current in any phase as a percentage of CT primary rating for the range 10 to 100% is displayed on this
bargraph indicator. If current in all phases is below 10% of CT rating, all segments will be off. For currents above 100% of
CT rating all segments will be on. All segments up to the actual current will be on for values between 10 and 100%.
For example:
CT RATING: 200:5
PHASE PICKUP: 70% of CT (LO)
PHASE CURVE: Normal inverse-LO
ACTUAL CURRENT: 165 A
DISPLAY: 165/200 = 83%
10% - 80% on
83% > 70% pickup so PHASE PICKUP indicator is flashing
Содержание 735
Страница 10: ......
Страница 12: ......
Страница 16: ...iv 735 737 Feeder Protection Relay GE Power Management TABLE OF CONTENTS ...
Страница 46: ...3 18 735 737 Feeder Protection Relay GE Power Management 3 6 SETUP EXAMPLE 3 SETUP AND OPERATION 3 ...
Страница 90: ...5 28 735 737 Feeder Protection Relay GE Power Management 5 5 IEC CURVES 5 OVERCURRENT CURVES 5 ...
Страница 92: ...6 2 735 737 Feeder Protection Relay GE Power Management 6 1 PROCEDURES 6 TESTING 6 Figure 6 1 TEST SETUP ...
Страница 98: ...6 8 735 737 Feeder Protection Relay GE Power Management 6 2 TEST RECORDS 6 TESTING 6 ...
Страница 100: ...7 2 735 737 Feeder Protection Relay GE Power Management 7 1 SETTINGS TABLE 7 COMMISSIONING 7 ...
Страница 108: ...iv 735 737 Feeder Protection Relay GE Power Management INDEX ...
Страница 109: ...GE Power Management 735 737 Feeder Protection Relay NOTES ...