CHAPTER 1: INTRODUCTION
SPECIFICATIONS
345 TRANSFORMER PROTECTION SYSTEM – QUICKSTART GUIDE
13
EAC
The EAC Technical Regulations (TR) for Machines and Equipment apply to the Customs
Union (CU) of the Russian Federation, Belarus, and Kazakhstan
Shock & Bump
IEC60255-21-2
Class 1
Seismic
IEC60255-21-3
Class 2
Power magnetic Immunity
IEC61000-4-8
Level 5
Pulse Magnetic Immunity
IEC61000-4-9
Level 4
Damped Magnetic Immunity IEC61000-4-10
Level 4
Voltage Dip & interruption
IEC61000-4-11
0,40,70,80% dips,250/300cycle
interrupts
Damped Oscillatory
IEC61000-4-12
2.5KV CM, 1KV DM
Conducted RF Immunity 0-
150khz
IEC61000-4-16
Level 4
Voltage Ripple
IEC61000-4-17
15% ripple
Ingress Protection
IEC60529
IP40 front , IP10 Back
Environmental (Cold)
IEC60068-2-1
-40C 16 hrs
Environmental (Dry heat)
IEC60068-2-2
85C 16hrs
Relative Humidity Cyclic
IEC60068-2-30
6day variant 2
EFT
IEEE/ANSI C37.90.1
4KV, 2.5Khz
Damped Oscillatory
IEEE/ANSI C37.90.1
2.5KV,1Mhz
RF Immunity
IEEE/ANSIC37.90.2
35V/m (max field), (80MHz-1GHz
with 1KHz sine and 80% AM
modulation)
ESD
IEEE/ANSIC37.90.3
8KV CD/ 15KV AD
UL508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
UL1053
e83849 NKCR
APPROVALS
Applicable Council Directive
According to
Low voltage directive
EN60255-5 / EN60255-27 / EN61010-1
CE compliance
EMC Directive
EN60255-26 / EN50263
EN61000-6-2
UL508
North America
cULus
UL1053
C22.2.No 14
EAC
Machines and Equipment
TR CU 010/2011
ISO
Manufactured under a registered
quality program
ISO9001
Item
Description
Country of origin
Spain or Canada; see label on the unit
Date of manufacture
See label on the side of the 345 unit
Declaration of Conformity and/or Certificate of
Conformity
Available upon request
TESTING AND CERTIFICATION
TEST
REFERENCE STANDARD
TEST LEVEL
Содержание 345
Страница 42: ...36 345 TRANSFORMER PROTECTION SYSTEM QUICKSTART GUIDE ELECTRICAL INSTALLATION CHAPTER 2 INSTALLATION...
Страница 73: ...CHAPTER 3 INTERFACES SOFTWARE SETUP 345 TRANSFORMER PROTECTION SYSTEM QUICKSTART GUIDE 67...
Страница 74: ...68 345 TRANSFORMER PROTECTION SYSTEM QUICKSTART GUIDE SOFTWARE SETUP CHAPTER 3 INTERFACES...