PRODUCT DESCRIPTION
2.3.3. LATCHING
RELAY
RATED VOLTAGE
Latching relay option 1
48 VDC
Latching relay option 2
125 VDC
Latching relay option 3
220 VDC
OPERATION RANGES
Operation range
80 % to 150 % of rated voltage
Consumption
8 W at rated voltage
Pickup value
60% of rated voltage
OPERATING TIME (at rated voltage)
Close time (N.O. contact)
< 25 ms.
Open time (N.C. contact)
< 20 ms.
CONTACTS
Continuous current
10 A continuous
20 A during 1 minute
200 A during 1 second
Make and carry
30 A
Breaking
5000 VA non inductive at 250 Vac
375 W inductive at 125 Vdc.
250 W inductive at 250 Vdc.
ENVIRONMENTAL
Temperature range
-20ºC to +60ºC
Maximum relative humidity
95%
Dielectric Withstand
Between independent circuits 2500 Vca one minute
Between circuits and ground 2500 Vca one minute
Between open contact
terminals
1800 Vca one minute
Mechanical life
More than 10 million operations
2.3.4. ENVIRONMENTAL
Operating Temperatures:
-20º C to +60º C
Ambient Storage Temperatures:
-40º C to +80º C
Maximum relative humidity
95%
Altitude
2000 m. Max
Pollution Degree
2
GEK-113064
HID High Impedance Differential Module
2-3