GE Zenith Controls ZBTS10 2 Скачать руководство пользователя страница 1

PB-5066 (6/04)

Since its introduction, the 

GE

Zenith 

ZTS

Series of

transfer switches has become a hallmark of quality
and performance.  Reliability resulting from superior
design and heavy duty construction has made the

ZTS

the industry standard for critical installations.

Our emphasis on research and development, design
improvements, materials, manufacturing methods,
quality assurance, and service yields products that have
been proven in hundreds of thousands of applications.

Subsequent to the first 

ZTS

units installed, our engin-

eering staff has been dedicated to the improvement
and expansion of our line. Today, 

GE

Zenith offers the

widest selection of transfer switch products worldwide.

ZTS

Automatic Transfer Switches

40-4000 Amps 

ZTSD

Delayed Transition Transfer Switches

40-4000 Amps

ZTSCT

Closed Transition Transfer Switches

100-4000 Amps

ZBTS

Automatic Transfer/Bypass Switches

100-4000 Amps

ZBTSD

Delayed Transition Bypass Switches

100-4000 Amps

ZBTSCT

Closed Transition Bypass Switches

100-4000 Amps

All 

ZTS

products meet or exceed industry requirements

allowing specification and installation confidence.

UL

1008 listed through 480 

VAC

CSA

C22.2 No. 178 listed through 600 

VAC

IEC

947-6-1 listed through 480 

VAC

ZTS

Series

Automatic Transfer Switches

Codes and Standards

NFPA

70, 99, 101, 110

IEEE

446, 241

NEC

517, 700, 701, 702

NEMA

ICS2-447

Controls tested in accordance with:

IEEE

472 (

ANSI

C37.90A)

EN

55022 Class B (

CISPR

11)

(Exceeds 

EN

55011 & 

MILSTD

461 Class 3)

EN

61000-4-2 (Level 4)

EN

61000-4-3 (

ENV

50140) 10 v/m

EN

61000-4-4

EN

61000-4-5, 

IEEE

C62.41 (1.2 X 50

m

s, 5

&

8 kV)

EN

61000-4-6 (

ENV

50141)

EN

61000-4-11

Enclosures meet the requirements of:

UL

508, 50

ANSI

C33.76

ICS

6

NEMA

250

Quality System: 

ISO

9001 Registered

Product Bulletin

GE Zenith Controls

e

Specification

Assistance

GE

Zenith offers a complete

range of product guide
specifications to help you
determine your needs.

For more information,
please consult your local 

GE

Zenith representative, 

our factory or our website 
at 

www.geindustrial.com

.

Содержание ZBTS10 2

Страница 1: ...s ZBTSD Delayed Transition Bypass Switches 100 4000 Amps ZBTSCT Closed Transition Bypass Switches 100 4000 Amps All ZTS products meet or exceed industry requirements allowing specification and installation confidence UL 1008 listed through 480 VAC CSA C22 2 No 178 listed through 600 VAC IEC 947 6 1 listed through 480 VAC ZTS Series Automatic Transfer Switches Codes and Standards NFPA 70 99 101 110...

Страница 2: ...Mechanism All GE Zenith ZTS switches employ the simple over center principle to achieve a mechanically locked position in either normal or emergency and GE Zenith s high speed drive assures contact transfer in 100 ms or less High contact pressure and positive mechanical lock allow for high withstand and closing ratings far exceeding UL requirements All ZTS units are listed with UL umbrella breaker...

Страница 3: ... tested synchronous logic automatically measures phase angle and frequency allowing disturbance free transfer Unsurpassed statistical ATS System monitoring available in real time T3 W3 elevator pre signal Automatically bypassed if the selected source fails minimizing time an elevator is without power Universal Motor Disconnect UMD sends a pre signal post signal or both to any motor control center ...

Страница 4: ...ENS MSPES MPSGS 2 2 2 2 2 2 2 2 3 3 2 2 2 2 2 2 2 2 2 2 2 2 Group Packages 2 2 3 Standard Accessory included in the group package Optional Accessory not included but can be added to group package Optional Accessory Can not be used with accessory having the same symbol N A Denotes an Accessory with 2 circuits as a standard Denotes an Accessory with 3 circuits as a standard Delayed Transition Units ...

Страница 5: ...h or without load CDT Exerciser no load timer Increased functionality no longer requires a jumper CTAP Chicago transfer alarm panel mounted in door of enclosure Includes 3 aux contacts and fuse DS Disconnect Switch Disconnects source voltage to transfer power panel DT DelayedTransition Only Time Delay from Neutral Switch position to Source 1 on retransfer DW DelayedTransition Only Time Delay from ...

Страница 6: ...ult standard R50 In Phase monitor between Normal Source 1 and Emergency Source 2 to allow transfer S5P Microprocessor activated auto manual retransfer selector switch for trnsferring to Normal Source 1 includes microprocessor activated YN accessory S12P Microprocessor activated auto manual retransfer selector switch for trnsferring to Normal Source 1 includes microprocessor activated YN YE accesso...

Страница 7: ...0 35 000 ZTSD8 2 80 100 800 50 000 42 000 35 000 35 000 ZTSD10 2 100 125 800 50 000 42 000 35 000 35 000 ZTSD15 2 150 200 800 50 000 42 000 35 000 35 000 ZTSD22 2 225 300 800 50 000 42 000 35 000 35 000 ZTSD26 2 260 350 800 50 000 42 000 35 000 35 000 ZTSD40 2 400 600 800 50 000 42 000 35 000 35 000 1 For each rating attained in above table the heat run was performed after the overload and enduran...

Страница 8: ...00 2500 100 000 85 000 100 000 85 000 ZTSD300 2 3000 4000 4000 100 000 85 000 100 000 85 000 ZTSD400 2 4000 6000 5000 100 000 85 000 100 000 85 000 GE Zenith Model No UL 1008 ZTS Switch Rating GE Zenith ZTS Switches Rated for Total Systems or Motor Loads 1 Withstand and Closing Current Ratings per UL 1008 and CSA Maximum Fuse Size Amps Maximum Circuit Amps at 480 VAC UL Maximum Circuit Amps at 600...

Страница 9: ...t the GE Zenith factory 7 Packing materials must be added to weights shown Allow 15 additional weight for cartons skids crates etc 8 Add 4 in height for removable lifting lugs 9 Lug adapters for 3000 4000 amp limits may be staggered length for ease of entrance Consult the GE Zenith factory for details 10 Ventilation louvers on both sides of enclosure at 3000 and 4000 amps One must be clear for air...

Страница 10: ...oval after load bypass In this way the transfer switch and or the control panel may be tested isolated and removed for maintenance without load interruption Then choose additional accessories 0 0 8 80 amps 0 1 0 100 amps 0 1 5 150 amps 0 2 0 200 amps 0 2 2 225 amps 0 260 amps 4 0 400 amps 0 6 0 600 amps 0 8 0 800 amps 0 0 0 1000 amps 1 2 0 1200 amps 1 6 0 1600 amps 1 0 0 2000 amps 2 6 0 2600 amps ...