background image

GE

 

Security 

R Series Remote Annunciators 

and Expander Installation and 

Operation Guide 

P/N 3100969 • REV 1.0 • ISS 15JUL08 

 

Содержание RLCD

Страница 1: ...GE Security R Series Remote Annunciators and Expander Installation and Operation Guide P N 3100969 REV 1 0 ISS 15JUL08 ...

Страница 2: ...dors of the respective products Intended use Use this product only for the purpose it was designed for refer to the data sheet and user documentation for details For the latest product information contact your local supplier or visit us online at www gesecurity com FCC compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of ...

Страница 3: ...lation features and controls 1 Installing annunciators and expanders 3 Wiring diagrams 6 Troubleshooting 8 Specifications 9 Operating the LCD models 10 Operating the LED models 12 Reading LCD displays 14 System Normal screen 14 Event Message screen 14 Details screen 15 Entering a password 16 Message priorities 17 Index 19 ...

Страница 4: ......

Страница 5: ...s of each model Table 2 is a complete list of all models and accessories in the series Figure 1 Models in the R Series Controls Enabled Ack Silence Lamp Test Power Fire Alarm Supervisory Ground Fault Trouble RLCD Controls Enabled Ack Silence Reset Signal Silence Drill Lamp Test Power Fire Alarm Supervisory Ground Fault Trouble RLCD C Controls Enabled Ack Silence Reset Signal Silence Drill Lamp Tes...

Страница 6: ...nciator with common controls English Red RLCD CF Remote Annunciator LCD text annunciator with common controls French RLED C Remote Annunciator 16 pair LED zone annunciator with common controls English RLED CR Remote Annunciator 16 pair LED zone annunciator with common controls English Red RLED CF Remote Annunciator 16 pair LED zone annunciator with common controls French RLED24 Remote Expander 24 ...

Страница 7: ...on LEDs Mounting slot DIP switch Remote key switch terminals Power terminals Expander cable terminals Figure 3 Expander rear view showing terminals V OUT V F E D C B A V IN V F E D C B A Expander cable terminals Mounting slot Expander cable terminals Table 3 DIP switch settings Switch Description and values S1 to S5 Network address The annunciator network address in binary The factory setting is f...

Страница 8: ...nstallation and Operation Guide Table 4 Examples of DIP switch address settings Address Settings Address Settings 1 1 2 3 4 5 6 7 8 ON 5 1 2 3 4 5 6 7 8 ON 2 1 2 3 4 5 6 7 8 ON 6 1 2 3 4 5 6 7 8 ON 3 1 2 3 4 5 6 7 8 ON 7 1 2 3 4 5 6 7 8 ON 4 1 2 3 4 5 6 7 8 ON 8 1 2 3 4 5 6 7 8 ON ...

Страница 9: ...e or within 20 feet 6 1 m of the enclosure with the cabling installed in conduit To install an annunciator 1 Secure the mounting ring to the electrical box as shown in Figure 4 2 Use the DIP switch to set the correct network address and baud rate See Table 3 for DIP switch settings 3 Connect the RS 485 riser to the appropriate annunciator terminals as per Figure 5 Class A or Figure 6 Class B Tip L...

Страница 10: ...le to the expander Attach an expander cable for interconnection to a second expander if applicable See Figure 7 4 Tilt the expander up and slide the mounting slot onto the top flange of the mounting ring 5 Tilt the expander down and push the bottom of the annunciator over the stud nut as shown in Figure 4 6 Secure the bottom of the annunciator to the mounting ring using the captive screw 7 Cover t...

Страница 11: ... expanders R Series Remote Annunciators and Expander Installation and Operation Guide 5 Figure 4 Installing the mounting ring annunciator and expander RS 485 RISER EXPANDER CABLE ANNUNCIATOR EXPANDER MOUNTING RING ELECTRICAL BOX ...

Страница 12: ...OUND 24V OUT 24V OUT 24 VDC LISTED 24 VDC SUPPLY 24 VDC Annunciator CH2 OUT CH2 OUT CH2 IN CH2 IN CH1 OUT CH1 OUT CH1 IN CH1 IN 24V IN 24V IN GROUND 24V OUT 24V OUT CH2 CH2 CH1 CH1 FACP RS 485 Figure 6 Class B wiring Annunciator CH2 OUT CH2 OUT CH2 IN CH2 IN CH1 OUT CH1 OUT CH1 IN CH1 IN 24V IN 24V IN GROUND 24V OUT 24V OUT 24 VDC LISTED 24 VDC SUPPLY 24 VDC FACP Annunciator CH2 OUT CH2 OUT CH2 IN...

Страница 13: ...V V OUT First Expander A B C D E F V V IN A B C D E F V V OUT Second Expander A B C D E F V V IN A B C D E F V V OUT Figure 8 Remote key switch wiring Annunciator KEYSWITCH KEYSWITCH RKey TB1 2 TB1 1 Note Remote key switch wiring is not supervised The key switch must be located within 20 feet 6 1 m of the annunciator and installed in conduit ...

Страница 14: ...m Cause Panel detail display Annunciator 000 Communication Fault Communication wiring has an open fault Communication wiring polarity is reversed Annunciator has no power Annunciator address DIP switches are set incorrectly on the annunciator shown in the panel message Annunciator network baud rate DIP switch is set incorrectly for normal operation use 9600 baud Annunciator LCD and LEDs are inoper...

Страница 15: ... mA RLCDF 113 mA RLCD C RLCD CR 115 mA RLCD CF 115 mA RLED C RLED CR 62 mA RLED CF 62 mA RLED24 RLED24R 34 mA RS 485 communications Class A or Class B 9600 baud Data wiring 18 to 14 AWG 1 0 to 2 5 sq mm twisted pair 6 twists per foot minimum Maximum wire run is 4 000 ft 1 219 m Remote key switch circuit 5 VDC at 1 mA power limited unsupervised Ground fault impedance 0 Ω Power wiring 18 to 14 AWG 1...

Страница 16: ...ators for RLCD RLCD R RLCDF Controls Enabled Ack Silence Reset Signal Silence Drill Lamp Test Power Fire Alarm Supervisory Ground Fault Trouble 7 9 11 5 8 10 12 6 14 13 15 2 3 4 1 Figure 10 Controls and indicators for RLCD C RLCD CR RLCD CF Controls Enabled Ack Silence Lamp Test Power Fire Alarm Supervisory Ground Fault Trouble 7 9 11 5 8 10 6 15 2 3 4 1 ...

Страница 17: ...ed 10 Controls Enabled LED Yellow LED that indicates the controls in that group are enabled at the annunciator Enabling the controls requires the level 2 password or the enable controls key 11 Ack Silence LED button Silences the panel buzzer and acknowledges all current events The LED next to the button indicates the function is active Requires the level 2 password or the enable controls key to op...

Страница 18: ...perating the LED models Figure 11 Controls and indicators for RLED C RLED CR RLED CF Controls Enabled Ack Silence Reset Signal Silence Drill Lamp Test Power Fire Alarm Supervisory Ground Fault Trouble 7 9 11 5 8 10 12 6 14 13 15 2 3 4 1 Figure 12 Controls and indicators for the RLED24 and RLED24R 2 3 4 1 ...

Страница 19: ...bled LED Yellow LED that indicates the controls in that group are enabled at the annunciator Enabling the controls requires the level 2 password or the enable controls key 11 Ack Silence LED button Silences the panel buzzer and acknowledges all current events The LED next to the button indicates the function is active Requires the level 2 password or the enable controls key to operate 12 Reset LED...

Страница 20: ... Banner lines Your facility name if programmed and the message System Normal Event Message screen The LCD display shows the Event Message screen when the control panel enters the fire alarm supervisory monitor trouble disablement or test state Use the up and down cursor buttons to scroll through the messages in the queue HH MM SS AXXX DXXX NNN SSSSSSSSSS RRR MESSAGE LINE 1 XXXXX MESSAGE LINE 2 XXX...

Страница 21: ...es details about the zone or device that generated the selected event message If the selected event message is for a zone the Details display screen shows which devices in the zone are active 1 Scrolling symbols The symbols at the right of the screen title line show whether there are more detail messages before or after the current message Use the up and down cursor buttons to scroll through the d...

Страница 22: ...rsor buttons to select a number or the Enter button to select a number and move to the next position To enter a password 1 Press any of the control buttons The system displays the Enter Password screen with the cursor in the first position of the four digit password field 2 Press the up or down cursor button to scroll through the numbers until the correct number appears 3 Press the Enter button to...

Страница 23: ...ding to the event type and the order of event occurrence The priority of event types is shown in the following lists US market place 1 Fire alarm events 2 Supervisory events and Trouble events 3 Other monitor events Canadian market place 1 Fire alarm events 2 Supervisory events 3 Trouble events 4 Other monitor events European market place 1 Fire alarm events 2 Supervisory events 3 Trouble events 4...

Страница 24: ......

Страница 25: ... 12 RLED CF 12 RLED CR 12 Controls Enabled LED 11 13 16 current 9 D D XXX 15 data wiring 9 date 14 description labels 13 Details screen 15 device address 15 description 13 message 15 dimensions 9 DIP switch 1 3 disabled points 14 down cursor button 11 Drill LED button 11 13 E electrical boxes 2 5 9 enclosures 2 3 Enter button 11 Enter Password screen 16 entering passwords 16 event message prioriti...

Страница 26: ... events 17 P P XX 15 panel address 15 passwords 16 PCD address 15 Power LED 11 13 power supplies 2 power wiring 9 priorities 17 R remote key switch 2 1 3 7 Reset LED button 11 13 RLCD controls and indicators 10 RLCD C controls and indicators 10 RLCD CF controls and indicators 10 RLCD CR controls and indicators 10 RLCDF controls and indicators 10 RLCD R controls and indicators 10 RLED24 controls an...