5-58
L60 Line Phase Comparison System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
IEC NETWORK CLIENT
ADDRESSES
The L60 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the L60 can connect.
A maximum of two simultaneous connections are supported at any given time.
p) IEC 60870-5-103 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-103
The L60 is provided with optional IEC 60870-5-103 communications capability. This feature is specified as
a software option at the time of ordering. See the
Order Codes
section in chapter 2 for details.
The IEC 60870-5-103 protocol is enabled when the
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
PROTOCOL
set-
ting is set to IEC 60870-5-103.
IEC103 COMMON ADDRESS OF ASDU
: This setting uniquely defines this L60 on the serial line. Select an ID between 0 and
254. This ID does not need to be in sequential order for all stations that communicate with a controller, but it is recom-
mended. Note that RS485 only allows a maximum of 32 slave stations on a communication line, so the entire range of 254
addresses is never exhausted.
IEC103 SYNC TIMEOUT
: This setting defines the time that the L60 waits for a synchronization message. The L60 synchro-
nizes its clock using all available sources, with the source synching more frequently overwriting the time of the other
sources. Since the synchronization message received from the IEC 60870-5-103 master is less frequent than IRIG-B, PTP,
or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and
none of IRIG-B, PTP, or SNTP is active, the L60 sets the invalid bit in the time stamp of a time-tagged message.
IEC NETWORK
CLIENT ADDRESSES
CLIENT ADDRESS 1:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 2:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 3:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 4:
0.0.0.0
Range: Standard IPV4 address format
MESSAGE
CLIENT ADDRESS 5:
0.0.0.0
Range: Standard IPV4 address format
IEC103
PROTOCOL
IEC103 COMMON
ADDRESS OF ASDU: 0
Range: 0 to 254 in steps of 1
MESSAGE
IEC103 SYNC TIMEOUT:
1
Range: 1 to 1440 min in steps of 1
MESSAGE
IEC103 INPUTS
BINARY
Range: see sub-menu below
MESSAGE
IEC103 INPUTS
MEASURANDS
Range: see sub-menu below
MESSAGE
IEC103 COMMANDS
Range: see sub-menu below
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...