5.6 GROUPED ELEMENTS
5
5.6.7 VOLTAGE ELEMENTS
a) MAIN MENU
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
VOLTAGE ELEMENTS
These protection elements can be used for a variety of applications such as:
•
Undervoltage Protection:
For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a specified time
delay.
•
Permissive Functions:
The undervoltage feature may be used to block the functioning of external devices by operat-
ing an output relay when the voltage falls below the specified voltage setting. The undervoltage feature may also be
used to block the functioning of other elements through the block feature of those elements.
•
Source Transfer Schemes:
In the event of an undervoltage, a transfer signal may be generated to transfer a load
from its normal source to a standby or emergency power source.
The undervoltage elements can be programmed to have a definite time delay characteristic. The definite time curve oper-
ates when the voltage drops below the pickup level for a specified period of time. The time delay is adjustable from 0 to
600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char-
acteristic.
The undervoltage delay setting defines the family of curves shown below.
(EQ 5.17)
where:
T
= operating time
D
= undervoltage delay setting (
D
= 0.00 operates instantaneously)
V
= secondary voltage applied to the relay
V
pickup
= pickup level
VOLTAGE ELEMENTS
PHASE
UNDERVOLTAGE1
MESSAGE
PHASE
UNDERVOLTAGE2
MESSAGE
NEUTRAL OV1
MESSAGE
NEUTRAL OV2
MESSAGE
NEUTRAL OV3
MESSAGE
AUXILIARY UV1
MESSAGE
AUXILIARY UV2
MESSAGE
AUXILIARY OV1
MESSAGE
AUXILIARY OV2
T
D
1
V
V
pickup
------------------
–
⎝
⎠
⎛
⎞
----------------------------------
=
Содержание C60
Страница 2: ......
Страница 4: ......
Страница 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Страница 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 98: ...3 48 C60 Breaker Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 390: ...8 18 C60 Breaker Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...