GE Multilin
C60 Breaker Protection System
7-3
7 COMMANDS AND TARGETS
7.1 COMMANDS
7
7.1.5 RELAY MAINTENANCE
PATH: COMMANDS
ÖØ
RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
The
PERFORM LAMPTEST
command turns on all faceplate LEDs and display pixels for a short duration. The
UPDATE
ORDER CODE
command causes the relay to scan the backplane for the hardware modules and update the order code to
match. If an update occurs, the following message is shown.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the
ORDER
CODE NOT UPDATED
message will be shown.
The
SERVICE COMMAND
is used to perform specific C60 service actions. Presently, there is only one service action avail-
able. Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than “101”
is entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in
the background while the C60 is running, and diagnostic information is stored on the non-volatile memory from time to time
based on the self-checking result. Although the diagnostic information is cleared before the C60 is shipped from the factory,
the user may want to clear the diagnostic information for themselves under certain circumstances. For example, it may be
desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self-
checking variables are reset to their initial state and diagnostics will restart from scratch.
COMMANDS
RELAY MAINTENANCE
PERFORM LAMPTEST?
No
Range: No, Yes
UPDATE ORDER CODE?
No
Range: No, Yes
SERVICE COMMAND:
0
Range: 0, 101
UPDATING...
PLEASE WAIT
Содержание C60 UR series
Страница 2: ......
Страница 4: ......
Страница 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Страница 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Страница 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 98: ...3 48 C60 Breaker Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3...
Страница 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Страница 390: ...8 18 C60 Breaker Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8...
Страница 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Страница 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Страница 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...