CHAPTER 3: INSTALLATION
SET UP CYBERSENTRY AND CHANGE DEFAULT PASSWORD
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
3-55
3
3.9 Set up CyberSentry and change default password
If and when first using CyberSentry security, use the following procedure for set up.
1.
Log in to the relay as Administrator by using the
VALUE
keys on the front panel or through EnerVista connected serially
(so that no IP address is required). If logging in through EnerVista choose Device authentication. Enter the default
password "ChangeMe1#". Note that the "Lock relay" setting needs to be disabled in the
Security > Supervisory
menu.
When this setting is disabled, configuration and firmware upgrade are possible. By default, this setting is disabled.
2.
Enable the Supervisor role if you have a need for it.
3.
Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4.
Log out of the Administrator account by choosing None.
Next, device or server authentication can be chosen on the login screen, but the choice is available only in EnerVista. Use
device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator, Observer).
When using a serial connection, only Device authentication is supported. When Server authentication is required,
characteristics for communication with a RADIUS server must be configured on the UR. This is possible only through the
EnerVista software. The RADIUS server itself also must be configured. At the end of this instruction manual, the appendix
called RADIUS Server gives an example of how to setup a simple RADIUS server. Once both the RADIUS server and the
parameters for connecting UR to the server have been configured, you can choose Server authentication on the login
screen of EnerVista.
Figure 3-61: Login screen for CyberSentry
During the commissioning phase, you have the option to bypass the use of passwords. Do so by enabling the Bypass
Access setting under
Settings > Product Setup > Security > Supervisory
. Be sure to disable this bypass setting after
commissioning the device.
You can change the password for any role either from the front panel or through EnerVista.
If using EnerVista, navigate to
Settings > Product Setup > Security
. Change the
Local Administrator Password
, for
example. It is strongly recommended that the password for the Administrator be changed from the default. Changing the
passwords for the other three roles is optional.
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...