Figure 5-103: Ground distance zones 2 and higher logic
Ground directional supervision
A dual (zero-sequence and negative-sequence) memory-polarized directional supervision applied to the ground distance
protection elements has been shown to give good directional integrity. However, a reverse double-line-to-ground fault can
lead to bad operation of the ground element in a sound phase if the zone reach setting is increased to cover high
resistance faults.
Ground distance zones 2 and higher use an additional ground directional supervision to enhance directional integrity. The
element’s directional characteristic angle is used as a maximum torque angle together with a 90° limit angle.
The supervision is biased toward operation in order to avoid compromising the sensitivity of ground distance elements at
low signal levels. Otherwise, the reverse fault condition that generates concern has high polarizing levels so that a correct
reverse fault decision can be reliably made.
The supervision for zones 2 and 3 is removed during open pole conditions.
837011AL.CDR
AND
AND
AND
OR
Quadrilateral
characteristic
only
AND
OR
MEMORY
V_1 > 0.80 pu
I_1 > 0.025 pu
SETTING
Enabled = 1
GND DIST Z2 FUNCTION
SETTING
Off = 0
GND DIST Z2 BLK
SETTING
IA
IB
DISTANCE SOURCE
IC
VAG
VBG
VCG
V_1
I_1
Wye
VT
s
SETTINGS
GND DIST Z2 ZOM/Z1 ANG
RUN
A ELEMENT
RUN
B ELEMENT
RUN
C ELEMENT
GND DIST Z2 POL CURRENT
GND DIST Z2 NON-HOMGEN ANG
GND DIST Z2 COMP LIMIT
GND DIST Z2 DIR RCA
GND DIST Z2 DIR COMP LIMIT
GND DIST Z2 VOLT LEVEL
GND DIST Z2 QUAD RGT BLD
GND DIST Z2 QUAD RGT BLD RCA
GND DIST Z2 QUAD LFT BLD
GND DIST Z2 QUAD LFT BLD RCA
TIMER
1 cycle
1 cycle
SETTING
GND DIST Z2 SUPV
RUN
| IN – 0.05 × I_1 | > Pickup
FLEXLOGIC OPERANDS
GND DIST Z2 PKP A
GND DIST Z2 DPO A
FLEXLOGIC OPERANDS
GND DIST Z2 PKP B
GND DIST Z2 DPO B
FLEXLOGIC OPERANDS
GND DIST Z2 PKP C
GND DIST Z2 DPO C
FLEXLOGIC OPERAND
GND DIST Z2 PKP
FLEXLOGIC OPERANDS
OPEN POLE OP ФA
OPEN POLE OP ФB
OPEN POLE OP ФC
D60, L60, and L90 only
GND DIST Z2 SUPN IN
GND DIST Z2 DIR SUPN
FLEXLOGIC OPERAND
OPEN POLE OP **
IN
I_2
I_0
GND DIST Z2 REV REACH
GND DIST Z2 REV REACH RCA
GND DIST Z2 REACH
GND DIST Z2 RCA
GND DIST Z2 ZOM/Z1 MAG
GND DIST Z2 Z0/Z2 ANG
GND DIST Z2 Z0/Z2 MAG
GND DIST Z2 SHAPE
GND DIST Z2 DIR
OR
** D60, L60, and L90 only
Содержание L60
Страница 130: ...4 30 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL LOGIC DIAGRAMS CHAPTER 4 INTERFACES 4 ...
Страница 464: ...5 334 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 498: ...7 10 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 570: ...10 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL DISPOSAL CHAPTER 10 MAINTENANCE 10 ...
Страница 582: ...A 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX C MISCELLANEOUS C ...
Страница 592: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...