5-128
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
Figure 5-53: Composite recloser curve with HCT disabled
With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding eight times pickup.
Figure 5-54: Composite recloser curve with HCT enabled
5.4.6.5 Standard recloser curves
The following graphs display standard recloser curves available for the L60.
NOTE
Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed.
If this is attempted, the EnerVista software generates an error message and discards the proposed changes.