5-230
L30 Line Current Differential System
GE Multilin
5.8 INPUTS AND OUTPUTS
5 SETTINGS
5
The
DIRECT INPUT 1-1(8) DEFAULT
setting selects the logic state of this particular bit used for this point if the local relay has
just completed startup or the local communications channel is declared to have failed. Setting
DIRECT INPUT 1-1(8) DEFAULT
to “On” means that the corresponding local FlexLogic™ operand (
DIRECT I/P 1-1(8)
) will have logic state “1” on relay startup
or during communications channel failure. When the channel is restored, the operand logic state reflects the actual state of
the corresponding remote direct output.
c) DIRECT OUTPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
DIRECT
DIRECT OUTPUTS
The relay provides eight direct outputs that are conveyed on communications channel 1 (numbered 1-1 through 1-8) and
eight direct outputs that are conveyed on communications channel 2 (numbered 2-1 through 2-8). Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific function (as selected by the user) to be transmitted.
Direct outputs 2-1 to 2-8 are only functional on three-terminal systems.
Figure 5–111: DIRECT INPUTS/OUTPUTS LOGIC
MESSAGE
DIRECT INPUT 2-8
DEFAULT: Off
Range: Off, On
DIRECT OUTPUTS
DIRECT OUTPUT 1-1:
Off
Range: FlexLogic™ operand
MESSAGE
DIRECT OUTPUT 1-2:
Off
Range: FlexLogic™ operand
MESSAGE
DIRECT OUTPUT 1-8:
Off
Range: FlexLogic™ operand
MESSAGE
DIRECT OUTPUT 2-1:
Off
Range: FlexLogic™ operand
MESSAGE
DIRECT OUTPUT 2-2:
Off
Range: FlexLogic™ operand
MESSAGE
DIRECT OUTPUT 2-8:
Off
Range: FlexLogic™ operand
NOTE
831024A1.CDR
SETTING
DIRECT OUTPUT 1-1:
(same for 1-2...1-8)
Off (Flexlogic Operand)
FLEXLOGIC OPERAND
DIRECT I/P 1-1
(same for 1-2...1-8)
L90-1
(87L is Enabled)
L90 communication channel
SETTING
DIRECT INPUT 1-1
DEFAULT:
(same for 1-2...1-8)
On
Off
ACTUAL VALUES
CHANNEL 1 STATUS:
Fail
OK
OR
SETTING
DIRECT OUTPUT 1-1:
(same for 1-2...1-8)
Off (Flexlogic Operand)
FLEXLOGIC OPERAND
DIRECT I/P 1-1
(same for 1-2...1-8)
L90-2
SETTING
DIRECT INPUT 1-1
DEFAULT:
(same for 1-2...1-8)
On
Off
Fail
OK
OR
ACTUAL VALUES
CHANNEL 1 STATUS:
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...