5.4 SYSTEM SETUP
5 SETTINGS
5
5.4.4 87L POWER SYSTEM
a) MAIN MENU
PATH: SETTINGS
SYSTEM SETUP
87L POWER SYSTEM
Any changes to the L30 power system settings will change the protection system configuration. As such,
the 87L protection at all L30 protection system terminals must be temporarily disabled to allow the relays
to acknowledge the new settings.
•
NUMBER OF TERMINALS:
This setting is the number of the terminals of the associated protected line.
•
NUMBER OF CHANNELS:
This setting should correspond to the type of communications module installed. If the relay
is applied on two terminal lines with a single communications channel, this setting should be selected as "1". For a two
terminal line with a second redundant channel for increased dependability, or for three terminal line applications, this
setting should be selected as "2".
•
CHARGING CURRENT COMPENSATION:
This setting enables and disables the charging current calculations and
corrections of current phasors. The voltage signals used for charging current compensation are taken from the source
assigned with the
CURRENT DIFF SIGNAL SOURCE 1
setting. As such, it's critical to ensure that three-phase line voltage is
assigned to this source. The following diagram shows possible configurations.
87L POWER SYSTEM
NUMBER OF TERMINALS:
2
Range: 2, 3
MESSAGE
NUMBER OF CHANNELS:
1
Range: 1, 2
MESSAGE
CHARGING CURRENT
COMPENSATN: Disabled
Range: Disabled, Enabled
MESSAGE
POS SEQ CAPACITIVE
REACTANCE: 0.100
k
Range: 0.100 to 65.535 k
in steps of 0.001
MESSAGE
ZERO SEQ CAPACITIVE
REACTANCE: 0.100
k
Range: 0.100 to 65.535 k
in steps of 0.001
MESSAGE
ZERO SEQ CURRENT
REMOVAL: Disabled
Range: Disabled, Enabled
MESSAGE
LOCAL RELAY ID
NUMBER: 0
Range: 0 to 255 in steps of 1
MESSAGE
TERMINAL 1 RELAY ID
NUMBER: 0
Range: 0 to 255 in steps of 1
MESSAGE
TERMINAL 2 RELAY ID
NUMBER: 0
Range: 0 to 255 in steps of 1
MESSAGE
CHNL ASYM COMP:
Off
Range: FlexLogic™ operand
MESSAGE
BLOCK GPS TIME REF:
Off
Range: FlexLogic™ operand
MESSAGE
MAX CHNL ASYMMETRY:
1.5 ms
Range: 0.0 to 10.0 ms in steps of 0.1
MESSAGE
ROUND TRIP TIME
CHANGE: 1.5 ms
Range: 0.0 to 10.0 ms in steps of 0.1
MESSAGE
IN-ZONE
TRANSFORMER
NOTE
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...