
5-54
L30 Line Current Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.10 DATA LOGGER
PATH: SETTINGS
PRODUCT SETUP
DATA LOGGER
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with
parameters
on the vertical axis and
time
on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Changing any setting affecting data logger operation will clear any data that is currently in the log.
DATA LOGGER
DATA LOGGER MODE:
Continuous
Range: Continuous, Trigger
MESSAGE
DATA LOGGER TRIGGER:
Off
Range: FlexLogic™ operand
MESSAGE
DATA LOGGER RATE:
60000 ms
Range: 15 to 3600000 ms in steps of 1
MESSAGE
DATA LOGGER CHNL
1:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
MESSAGE
DATA LOGGER CHNL
2:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
MESSAGE
DATA LOGGER CHNL
3:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
MESSAGE
DATA LOGGER CHNL 16:
Off
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
MESSAGE
DATA LOGGER CONFIG:
0 CHNL x
0.0 DAYS
Range: Not applicable - shows computed data only
Table 5–3: DATA LOGGER STORAGE CAPACITY EXAMPLE
SAMPLING RATE
CHANNELS
DAYS
STORAGE CAPACITY
15 ms
1
0.1
954 s
8
0.1
120 s
9
0.1
107 s
16
0.1
60 s
1000 ms
1
0.7
65457 s
8
0.1
8182 s
9
0.1
7273 s
16
0.1
4091 s
60000 ms
1
45.4
3927420 s
8
5.6
490920 s
9
5
436380 s
16
2.8
254460 s
3600000 ms
1
2727.5
235645200 s
8
340.9
29455200 s
9
303
26182800 s
NOTE
Содержание L30
Страница 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 58: ...2 28 L30 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 126: ...4 30 L30 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...6 26 L30 Line Current Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 450: ...10 10 L30 Line Current Differential System GE Multilin 10 4 INSTANTANEOUS ELEMENTS 10 APPLICATION OF SETTINGS 10 ...
Страница 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 644: ...x L30 Line Current Differential System GE Multilin INDEX ...