TOXIC/OXYGEN – TRANSMITTER

 (PCB 337) 

 

www.gds–technologies.co.uk

Technical Sheet ref C1882B

Electrochemical cells

Setting up a pre calibrated Transmitter  

(Cell replacement)

New sensors are supplied ready to connect to the system with all jumpers 

inserted. This procedure shows how to recalibrate as part of a routine 

maintenance or cell replacement.

1.  If bench testing the PCB see section B3

2.   Using a digital mV meter measure across test pins TP2/3 and 

adjust Zero pot RV2 until LED D9 goes green for 4mA (zero) = 4mV 
(sensor bridge zero) see B9

3.  Apply a known test gas to the sensor (e.g. 100ppm CO) for 1 

minute at a flow rate of 1 litre to give a 13mA = 11mV across test 
pins TP2/3, adjust gain pot RV4 for correct mV reading. 

 

Power supply

 

15 to 30Vdc 24v nominal 

Outputs

  

3 wire 4~20mA Direct (WPY) 
4 wire CANbus (Addressable) 4~20mA (Y)
Relays 

Low alarm  

SPCO 

(when fitted) 

High alarm  

SPCO  

0.5A @ 30Vdc 

 

Fault alarm  

SPCO

 

Inhibit option during servicing

Logging   

Intervals – variable time 

 

Roll over/stop 

 

Storage – 2,880 readings 

Requires 

USB A to USB micro B cable  

 

PC or laptop (dedicated) 

 

GDS Terminal (download from GDS website)

Setting up a new transmitter utilising 

GDS Terminal 

(download from GDS website)

1. Insert jumpers J10 and J9 position SO for 4-20mA source 

output.

2.  Connect sensor to J14 terminal W-white Y-yellow P-pink.
3.  For bench setup only – connect 24V + and 0V to J2, connect 

jumper to J1 (4~20mA output test load) remove after set up.

4.  Rotate Gain pot fully anti-clockwise (minimum span.)
5.  When in clean air the sensor bridge is zeroed by adjusting 

zero pot until LED D9 is Green.

6.  Connect PC to sensor via GDS terminal using USB-A to USB 

Micro-B cable at 4800 baud connected to J11.  The terminal 

output screen shows continuous data output/ commands and 

allows input from the PC keyboard.

7.  Select COM Port – Note each new sensor connected to 

requires a new COM Port to be connected to.

8.   Press ‘Space Bar’ loads sensor information. Ensure jumper J17 

is fitted before programming. Press (C) to enter Calibration 

Mode, and Press ($) to initialize the sensor. 

 

To update firmware contact GDS.

 

Press W to set 4-20mA parameters, use (L) and (H) to adjust 

4mA, Press ‘Space’ to set, use (L) and (H) to adjust the 20mA, 

press ‘Space’ to set.

9.  Then press (Z) on the PC to zero the reading.
10. Apply a known test gas to the sensor (e.g. 100ppm CO) for 

1 minute at a flow rate of 1 litre to give (e.g 12mV = 12mA) 

across test pins TP2/3, adjust gain pot for correct mV reading. 

11.  When using a PC press (S) to enter span mode and using (H) 

or (L) adjust the reading. Note – This adjusts the mA reading on 

TP2/3 when adjusted.

12.  Press (space) to exit span and then (X) to exit the calibration 

mode.

13.  Connect the sensor to a Combi alarm panel and ensure that it 

reports in correctly. 

Note: Fit the end of line (EOL) link J3 if the 

sensor is to be installed at the end of the sensor cable.

14. If the sensor is fitted with a display – adjust the contrast using  

‘VR1’ pot.

15.  Remove J1 test link for normal operation, (this does not need to 

be removed when used as an Addressable sensor)

16. Ensure J17 address link is removed (this is only used when 

changing address from the alarm panel).

17.  On completion and when used as an addressable sensor, 

future calibrations may be carried out at the Combi alarm 

panel.

NOTE: 

Oxygen cells only use the P+ and Y terminals J14.  

To adjust for the ‘Zero’ it is normal practice to disconnect the green 
connector on J14 and adjust the Zero pot until LED D9 is green and 
4mA across TP2/TP3. When the cell is reconnected in air at 20.9%Vol 
oxygen the span can be adjusted for 17.4mA reading across the same 
test pins using the gain pot. 
If an LCD option is fitted then calibration and other settings using 
magnets instead of a PC can be achieved. See over.

See Reverse for Full list of GDS Terminal Commands

A

C

B

Tox 

u/ma

Can Sensor

PCB 337

J12

J4

RELAYS

DISPLAY

SENSOR

CELL

J17

D3

D2

GAIN

J5

J14

J13

J15

+

-

RV2

J7

JTAG

VR1

S

J19

J18

J2

0

ZERO

GAIN

CONTRAST

ZERO

RV4

D9

TEST

J3

EOL

TP1

(W)

(P)

(Y)

ov

TP2

J1

TP10

J16

O2

O2

INV

D5

D10

PROG

ADD

4-20

J11

J10 J9

U14

TP3

4-20mA Pins (mV)

(Steps 2/3)

J9 + J10

(select sink/source)

GDS Terminal 

Connection  

(Micro USB B)

Gas Status LED 

(Step 2)

Gain Pot 20mA
(Step 3)

Zero Pot  

(Step 2) (4mA)

Insert jumper J16  

when using Oxygen Cells

Fig. 1