Velox to G-Shield Fire Upgrade Kit Instructions
5
Version 3
P/N 761011-02
6. Touchscreen display hardware upgrade procedure.
The touchscreen display must be configured to operate as a G-Shield Fire device. The
Velox PCBA must be carefully removed and the information stored in the touchscreen
display must be updated.
The touchscreen is reused for the G-Shield Fire and must be retained.
Do not lift one side more than the other. Small movements are best. The PCBA
must be removed without excessive force to avoid damage to the touchscreen
connector pins.
CAUTION:
Figure 4. G-Shield Fire Touchscreen PCBA image.
Figure 5. Spudger inserted - top view.
Lay the touchscreen display face down on a soft cloth with the Velox PCBA facing
upwards.
Step 1.
Carefully insert a suitable spudger between the touchscreen display and the PCBA.
Work the spudger around the gap and gently lever the two items apart.
Step 2.
Make sure the pins are undamaged.
Step 3.
Figure 6. Spudger inserted - edge view.
Figure 7. Touchscreen with undamaged connector pins.