Velox to G-Shield Fire Upgrade Kit Instructions
14
Version 3
P/N 761011-02
14. Wiring Diagram
Use stranded tinned copper conductors in a PVC jacket. Cable size of 16 AWG to 22 AWG is
suitable. The maximum allowable outside diameter (OD) is 6.5 mm. Use insulated bootlace
ferrules to avoid damage to the copper conductors.
15. Cable Information
Use four core sheathed cable between the touchscreen and the Sensor Platforms. The
maximum cable length permitted is 20 m.
You can use equivalent alternatives for this item.
Note:
Figure 26. G-Shield Fire system wiring diagram.
J3 and J4 are interchangeable.
Note:
Gastech recommends inline fuses for both power feeds. Refer to figure 26 for
the fuse values.
Note: