For more information & technical support:
35
F-Guard UV-IR-HD User Manual
76-M-6010-02-02
Approvals
Note: All items are designed and tested to meet the relevant requirements.
•
Explosion proof:
o
ATEX: II 2 G D
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C<Ta<75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -55°C<Ta<85°C
o
IECEx, PESO:
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -50°C
≤
Ta
≤
75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -50°C
≤
Ta
≤
85°C
o
FM & FMC:
Class I, Div. 1, Groups B, C & D; T4 Ta = -50°C
≤
Ta
≤
85°C or T5 Ta = -50°C
≤
Ta
≤
75°C
Class II/III, Div. 1, Groups E, F, G; T4 Ta = -50°C
≤
Ta
≤
85°C or T5 Ta = -50°C
≤
Ta
≤
75°C
Class I, Zone 1, AEx/Ex db IIC T4 Gb or Class I, Zone 1, AEx/Ex db eb IIC T4 Gb
T4 Ta = -50°C
≤
Ta
≤
85°C or T5 Ta = -50°C
≤
Ta
≤
75°C
and
Zone 21, AEx/Ex tb IIIC T95°C Db -50°C
≤
Ta
≤
75°C or
Zone 21, AEx/Ex tb IIIC T105°C Db -50°C
≤
Ta
≤
85°C
•
Performance:
o
ANSI FM 3260
o
EN 54-10
•
Functional safety: Meets the requirements for SIL 2 per IEC 61508.
•
California Fire Marshall
•
EAC CU TR
Electromagnetic Compatibility
The detector fully complies with EMC directive 2014/30/EU and protected against interference caused by RFI
and EMI. The cables to the detector must be shielded and the detector must be grounded in order to comply
to the EMC directive.
10. Performance
The following tables show test results of detection distances and times for different fire scenarios. Each table
lists results for a different sensitivity setting. For liquid fires the size of fire refers to the size of the pan, filled
with the fuel. For gas fires the length of the plume is listed.