Universal dimmer actuators GDA2K-400 KNX / GDA4K-400 KNX
pdated: Mai-17 (Subject to changes) Page 38 of 63
3.3.11
Hour counter and service
This page appears when
Activate operating hours counter
is selected on the
Configuration options
parameter page.
Table 17
Designation
Values
Description
Type of hour counter
Hour counter
Forward counter for duty cycle
of the channel.
Counter for time period before
next service
Backward counter for duty cycle
of the channel.
Hour counter
Reporting of operating hours
when changing (0..100 h, 0 = no
report)
0..100
Default value = 10
At what interval is the current
meter reading to be sent?
Example:
10 = Send each time the meter
reading increases by another 10
hours.
Report operating hours
cyclically
No
yes
Send at regular intervals?
Time for cyclical transmission
2 minutes, 3 minutes,
5 minutes, 10 minutes,
15 minutes, 20 minutes,
30 minutes, 45 minutes
60 Minutes
At what interval?
Counter for time period before next service
Service interval (0..2000, x10 h)
0..2000
Default value =
100
Desired timescale between 2
services.
Example:
10 = 10 x 10 h
= 100 hours
Reporting of changes to time to
service (0..100 h, 0 = no report)
0..100
Default value =
10
At what interval is the current
meter reading to be sent?
Example:
10 = Send each time the meter
reading decreases by another 10
hours.
Report time to service cyclically
no
Yes
Send
remaining
time to next
service at regular intervals?
Object
Time to next service
.