13-17-621 Page 91
Inlet Pressure
Feedback
This output can be used to monitor the current value of the analog input for inlet
pressure on machines that have an inlet pressure sensor. The scaling of the output
matches the scaling of the inlet pressure sensor. For most machines, this is as follows:
4 mA = 0 bar absolute and 20 mA = 1 bar absolute.
Airend Temperature
Feedback
This output can be used to monitor the current value of the temperature input for
airend discharge temperature. The scaling of the output is linear between 0 degrees C
and the factory maximum fault setting. On most machines, this will be equal to: 4 mA =
0 C (32 F) and 20 mA = 115.56 C (240 F).
Percent Load
Feedback
This output can be used to monitor the current value of percent load on a variable
speed machine. The scale of the output is linear between 4mA = 0% load and 20 mA =
100% load.
4.7 Advanced
There are five sub-menus in the
Advanced
settings menu:
Setup, Operating Limits, Control, Cooling,
and
Backup / Restore.
Table 42: Advanced Settings
Advanced Settings
Setting
Sub-Menu
Short Description
Advanced
The User can setup the Model Name, Serial Number, Design Pressure,
Max Volume Flow, Oil Type, System Voltage, Motor SFA, Elevation, Total
Hours, Loaded Hours and Brand
The User can set the operating limits for Max Start Pressure, Heavy
Startup, Minimum State Temperature, Discharge Temperature Warning,
Delivery Pressure Warning, Discharge Temperature Fault and Delivery
Pressure Fault.
The User can set the Automatic Stop Time, Rotation Direction Check, Min
Stop Time, Minimum Run Time, Acceleration Time and Star / Delta Time.
The User can set and select the Cooling Type and cooling Fan Control.
The User can set advanced control and cooling options for variable speed
drive, when applicable.
The User can set advanced PID tuning options.
The User can perform backup and restore tasks like Save User
Configuration, Restore User Configuration and Restore Factory Defaults.
Table 42 above lists the sub-menus of the
Advanced
settings menu.
4.7.1 Setup:
These settings are intended to be set/modified by authorized personnel having the Technician and Factory
Login. Please contact Gardner Denver for assistance if you are not sure about these settings. Figure 123
shows the
Advanced Setup
home screen.
Содержание Governor TEN014980
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View ...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol ...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics ...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally ...