PP600F/602F LED lighting controllers - User Manual
9.5.1
Setting continuous output (extended)
Set continuous output on a PP600F as follows:
The PP600F is ready. Press and hold
RANGE
for
one second.
Use the
p
and
q
buttons to select which output
channel to set up -
CH1
or
CH2
.
Press
SELECT
.
rAT
is displayed. Wait one second...
Use the
p
,
q
, and
RANGE
buttons to select the
maximum current rating of the LED unit.
Press
SELECT
.
Use the
p
and
q
buttons to select
CON
. Select
SE1
,
SE2
, or
SE12
for slected output (see
Section 9.3.1, Continuous output and selected
continuous output
). (PU1 is also displayed).
Press
SELECT
.
CUR
is displayed. Wait one second...
—
31
—