Controlling the central power supply via XML

G&D MultiPower-12-NT · 

21

English

Commands

Switch on a »Power Out« socket

Use the command 

<powerupoutlet>

 to switch on a specific »Power Out« socket of the 

central power supply.

Switching on a »Power Out« socket requires the following parameters:

Switch a »Power Out« socket off

Use the command 

<powerdownoutlet>

 to switch off a specific »Power Out« socket of 

the central power supply.

Switching off a »Power Out« socket requires the following parameters:

<MultiPowerSwitch>

Central power supply whose »Power Out« socketis switched on

<outlet>

No. of »Power Out« socket

SWITCHING ON A »POWER OUT« SOCKET

<?xml version="1.0" encoding="utf-8"?>

<root>

<powerupoutlet>

<MultiPowerSwitch>0x0000000A</MultiPowerSwitch>

<Outlet>1</Outlet>

</powerupoutlet>

</root>

<MultiPowerSwitch>

Central power supply whose »Power Out« socketis switched off

<outlet>

No. of »Power Out« socket

SWITCHING OFF A »POWER OUT« SOCKET

<?xml version="1.0" encoding="utf-8"?>

<root>

<powerdownoutlet>

<MultiPowerSwitch>0x0000000A</MultiPowerSwitch>

<Outlet>1</Outlet>

</powerdownoutlet>

</root>

Содержание MultiPower-12-NT

Страница 1: ...Guntermann Drunck GmbH www gdsys de G D MultiPower 12 NT A9100288 1 20 Installationsanleitung DE EN Installation Guide...

Страница 2: ...uss G D bernimmt keine Gew hrleistung f r Ger te die nicht bestimmungsgem eingesetzt wurden nicht autorisiert repariert oder modifiziert wurden schwere u ere Besch digungen aufweisen welche nicht bei...

Страница 3: ...zt Hochfrequenzenergie und kann diese ausstrahlen Wenn es nicht gem der Anleitung installiert wird kann es Funkst rungen ver ursachen Es wird jedoch keinerlei Garantie daf r bernommen dass die St run...

Страница 4: ...balen Netzwerkeinstellungen 12 Anschluss der zentralen Stromversorgung an das lokale Netzwerk 12 Start der Webapplikation 13 XML Steuerung der zentralen Stromversorgung 14 Aufbau eines g ltigen XML Do...

Страница 5: ...connected from all power sources Disconnect all power plugs and all power supplies of the device D branchez toutes les sources d alimentation Avant l installation assurez vous que l appareil a t d bra...

Страница 6: ...tgelieferten oder in der Bedienungsanlei tung aufgef hrten Netzteil Betreiben Sie das Ger t ausschlie lich im vorgesehenen Einsatzbereich Die Ger te sind f r eine Verwendung im Innenbereich ausgelegt...

Страница 7: ...ebrauchte Batterien d rfen nicht in den Hausm ll geworfen werden Beachten Sie die g ltigen Vorschriften zur Entsorgung elektronischer Produkte CAUTION Risk of explosion if the battery is replaced by a...

Страница 8: ...eroberfl che zur berwachung der zentralen Stromversorgung zur Verf gung In der Standardeinstellung schaltet die zentrale Stromversorgung alle 12 Power Outlets ein Sie haben die M glichkeit jede Power...

Страница 9: ...ises Inbetriebnahme 1 Schalten Sie den Netzschalter des internen Netzteils Main Power ein 2 Schalten Sie ggf den Netzschalter des internen Netzteils Red Power ein HINWEIS Maximal zw lf Ger te k nnen m...

Страница 10: ...e auf die umzuschaltende Power Out Buchse Schaltung via SNMP So schalten Sie eine Power Out Buchse via SNMP Setzen Sie das Managed Object outletStatus der zu schaltenden Power Out Buchse ber die SNMP...

Страница 11: ...ert ber einen Wechsler den Status der Stromversorgung Bei unterbrochener Spannungsversorgung ist der Wechsler auf Pin 3 Main Power bzw Pin 8 Red Power geschaltet Bei anliegender Spannung schaltet der...

Страница 12: ...maximal zul ssige Last berschritten leuchten zus tzliche eine bzw zwei rote LEDs Hinweis Eine hohe Temperatur im Ger teinneren wirkt sich nachteilig auf die Leistung des Ger tes aus K hlen Sie das Ge...

Страница 13: ...ower Out x Status an Die Spannung steht an diesem Ausgang bereit aus An diesem Ausgang steht keine Spannung zur Verf gung Im Falle einer berlast oder eines Kurzschlusses wird der Ausgang abgeschaltet...

Страница 14: ...ung Verwenden Sie hierzu ein Twisted Pair Kabel der Kategorie 5 oder h her 2 Stellen Sie sicher dass die IP Adresse der Netwerkschnittstelle des Rechners Teil des Subnetzes ist welchem auch die IP Adr...

Страница 15: ...des Administratorkontos Die voreingestellten Zugangsdaten zum Administratorkonto lauten Benutzername Admin Passwort siehe Login Information auf dem Etikett an der Ger teunterseite HINWEIS Das voreinge...

Страница 16: ...etzwerk an 1 Entfernen Sie die Twisted Pair Kabelverbindung zwischen dem Rechner und der zentralen Stromversorgung 2 Integrieren Sie die zentrale Stromversorgung in das lokale Netzwerk Betriebsmodus W...

Страница 17: ...den Systemvoraussetzungen der erfor derlichen Konfiguration der Netzwerkschnittstelle der MultiPower NT Ger te und zum Einsatz der Webapplikation finden Sie im separaten Handbuch Benutzername Geben S...

Страница 18: ...t plat ziert Ab Seite 21 werden die verschiedenen Befehle erl utert Auswahl der Ger te Die XML API bietet durchg ngig die M glichkeit Ger te nicht nur ber ihre ID sondern wahlweise auch ber ihren Name...

Страница 19: ...Im Attribut type ist der Name des ausgef hrten Befehls enthalten Beim Ausf hren mehrerer Befehle in einem XML Dokument siehe unten k nnen Sie so die Antwor ten den verschiedenen Befehlen zuordnen Im f...

Страница 20: ...ontainer ausgegeben Hierf r werden folgende Container benutzt Fehlermeldungen werden innerhalb des Containers Error ausgegeben Warnungen werden innerhalb des Containers Warning ausgegeben Erfolgsmeldu...

Страница 21: ...nitialisierungsvektor verschl sselt sind Passwort Verschl sselung In diesem Modus werden nur die Passw rter der Benutzer konten in den XML Antworten des G D Ger ts verschl sselt Hierf r wird ein Subse...

Страница 22: ...r UPD ber welches die XML Kommunikation abgewickelt wird Port Geben Sie den Port an ber welchen die XML Kommuni kation abgewickelt wird Die Ports 80 443 und 27996 werden f r andere Dienste ver wendet...

Страница 23: ...c ersetzt In diesem Container wird der Container CipherData erwartet der wiederum den Container CipherValue enth lt Der verschl sselte Datenblock CipherValue besteht aus der Kombination von Initiali s...

Страница 24: ...das letzte Byte des Padding die Anzahl hinzugef gter F llbytes angibt Die F llbytes selbst sind zuf llig zu w hlen Der Initialisierungsvektor wird f r Stromchiffren hier CBC ben tigt Er wird im Versc...

Страница 25: ...r die Ausschaltung einer Power Out Buchse sind folgende Parameter erforder lich MultiPowerSwitch Zentrale Stromversorgung deren Power Out Buchse eingeschaltet wird outlet Nr der Power Out Buchse EINSC...

Страница 26: ...die Angabe des gew nschten Monitoring Wertes k nnen Sie die Auflistung zus tzlich eingeschr nken MultiPowerSwitch Zentrale Stromversorgung deren Power Out Buchse resettet wird outlet Nr der Power Out...

Страница 27: ...name MultiPower NT name monitorName Temperature monitorName value 36 5 value alarm off alarm acknowledged no acknowledged item MultiPowerSwitch result root HINWEIS Neben dem Namen und Wert des jeweili...

Страница 28: ...60 50Hz 1 4 0 6 A redundante Stromversorgung Typ internes Netzteil Anschluss 1 Kaltger testecker IEC 320 C14 Stromaufnahme 100 240 VAC 60 50Hz 1 4 0 6 A Sonstige Schnittstellen Netzwerk 1 RJ45 Buchse...

Страница 29: ...Deutsch...

Страница 30: ...will not provide warranty for devices that Are not used as intended Are repaired or modified by unauthorized personnel Show severe external damages that was not reported on the receipt of goods Have b...

Страница 31: ...equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful inter ference to radio communications However there...

Страница 32: ...1 Configuring global network settings 12 Connecting the central power supply to the local network 12 Starting web application 13 Controlling the central power supply via XML 14 Structure of a valid XM...

Страница 33: ...que l appareil a t d branch de toutes les sources d alimentation D branchez toutes les fiches d alimentation et toutes les alimenta tions lectrique de l appareil Trennen Sie alle Spannungsversorgungen...

Страница 34: ...e this device with the provided G D power pack or with the power pack listed in the manual Operate the device only in designated areas The devices are designed for indoor use Avoid exposure to extreme...

Страница 35: ...not dispose of batteries in municipal waste Check local regulations for the disposal of electronic products ATTENTION Il y a danger d explosion s il y a remplacement incorrect de la batterie Mettre au...

Страница 36: ...rface to monitor the central power supply By default the central power supply switches on all 12 power outlets You can also switch each Power Out socket separately via Config Panel SNMP or text based...

Страница 37: ...r outlet of another power circuit Startup 1 Switch on the power switch of the internal Main Power power pack 2 Switch on the power switch of the internal Red Power power pack NOTE The MultiPower 12 NT...

Страница 38: ...ight 4 Click on the Power out socket you want to switch Switching via SNMP How to switch a Power Out socket via SNMP Set the managed object outletStatus of the Power Out socket you want to switch via...

Страница 39: ...show the status of the power supply If the power supply is interrupted the changer switches to pin 3 Main Power or pin 8 Red Power If the power supply is active the changer switches to pin 4 Main Powe...

Страница 40: ...the maximum load is exceeded one or two red LEDs light up Note If one or two red LEDs indicate that the temper ature within the device is too high make sure to cool the device Status Ready on Device i...

Страница 41: ...t off No voltage available at this output In case of an overload or a short circuit the output is disa bled but becomes active after 10 seconds Status 12VDC 800mA Power Out 2 Status 12VDC 800mA Power...

Страница 42: ...the network interface of any computer to the central power supply s Network interface 2 Make sure that the IP address of the computer s network interface is part of the subnet to which the IP address...

Страница 43: ...tor account s default password The default access data is Username Admin Password see login information on the label on the bottom of the device NOTE The default admin password for devices manufacture...

Страница 44: ...upply to the local network 1 Remove the twisted pair cabling between computer and the central power supply 2 Integrate the device into the local network Operating mode Enter the desired operating mode...

Страница 45: ...Login NOTE The separate manual provides information about system requirements the required configuration of the network interface at the MultiPower NT devices and the operation of the web application...

Страница 46: ...ecuted are placed between the start and end tag root The commands are described on page 21 Selecting devices The XML API lets you specify devices not only by their ID but also by their name Use the at...

Страница 47: ...in a result tag The attribute type includes the name of the executed command When executing several commands within the same XML document see below you can assign the responses to different commands I...

Страница 48: ...upply are shown in different XML containers The following containers are used for this purpose Error messages are included in the container Error Warnings are included in the container Warning Success...

Страница 49: ...tion vector Password encryption In this mode only passwords of user accounts in XML responses of the G D device are encrypted For this a subset of the XML encryp tion see page 19 is used When using XM...

Страница 50: ...ccess Select the protocol TCP or UPD to be used to process com munication via XML Port Enter the port to process XML communication Ports 80 443 und 27996 are used for other services They are not avail...

Страница 51: ...04 xmlenc In this container the container CipherData is expected which in turn contains the container CipherValue The encrypted data block CipherValue consists of the combination of initialization vec...

Страница 52: ...e last byte of the padding to indicate the number of added fill bytes The fill bytes can be chosen randomly The initialization vector is required for stream ciphers here CBC It is randomly selected wh...

Страница 53: ...ly Switching off a Power Out socket requires the following parameters MultiPowerSwitch Central power supply whose Power Out socketis switched on outlet No of Power Out socket SWITCHING ON A POWER OUT...

Страница 54: ...ring values You can further restrict the list by specifying the desired monitoring value MultiPowerSwitch Central power supply whose Power Out socket is reset outlet No of Power Out socket ResetDelay...

Страница 55: ...name MultiPower NT name monitorName Temperature monitorName value 36 5 value alarm off alarm acknowledged no acknowledged item MultiPowerSwitch result root NOTE In addition to the name and value of t...

Страница 56: ...0Hz 1 4 0 6 A Redundant power supply Type Internal power pack Connector 1 IEC plug IEC 320 C14 Power consumption 100 240 VAC 60 50Hz 1 4 0 6 A Other interfaces Network 1 RJ 45 socket Service 1 Mini US...

Страница 57: ...English...

Страница 58: ......

Страница 59: ...English...

Страница 60: ...bere Leimbach 9 57074 Siegen Germany www gdsys de sales gdsys de Das Handbuch wird fortlaufend aktualisiert und im Internet ver ffentlicht The manual is constantly updated and available on our website...

Отзывы: