Mapping Overview
Programming Overview
Figure 5.1 is a brief overview of the concept of mapping. The next several pages of the manual show these subjects in detail.
5.3.1 Input Point Mapping
Input points are assigned to input zones. Any input point can be assigned to any input zone. Input points can be assigned to one zone only. An
input point can be designated as “unused,” which means it has not been assigned to a zone.
5.3.2 Output Circuit Mapping
Figure 5.3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor
above/floor below application, see Figure 5.5.
1
3
2
1
2
3
4
5
In its simplest application, mapping determines which outputs are activated by which inputs.
input zone
output group
input points
(SLC devices)
output points
(NAC circuits)
Input zones are mapped by event type to output groups. Cadence
patterns are assigned as part of the mapping information. Up to eight
groups/patterns can be selected for each event.
input points
(SLC devices)
input zones
cadence
patterns
output groups
output points
(NAC/relay ckts)
Output points are assigned
to output groups only.
system trbl & special
system events
optional
Figure 5.1 Mapping Overview
NOTE:
Mapping cannot be programmed through the annunciators. It can only be programmed through the HFSS Honeywell Fire Software
Suite.
point 1
point 2
point 3
point 4
point 5
point 6
point 7
point 8
point 70
point 71
point 72
point 73
point 74
point 75
point 4
point 5
point 6
point 7
point 8
through
zone 1
zone 2
zone 3
zone 4
zone 5
zone 6
through
zone 123
zone 124
zone 125
Figure 5.2 Input Point Assignment Example
output circuit 1
NAC circuit
output circuit 2
aux power output
Aux power outputs are not
mapped to output groups.
group 1
group 2
through
group 124
group 125
output circuit 3
Relay 1
output circuit 4
Relay 2
In this example, all NAC outputs
are assigned to group 1.
JumpStart creates group 124 and
group 125 for Relay 1 and Relay 2.
Figure 5.3 Assigning Output Circuits to Groups (Example)