8.
POWER+
ROUTINE START
-
UP
8.1
Start-up after Shutdown
This section describes the start-up procedures for the operator after a POWER+ shutdown. After
shutdown, the UPS on, Alarm and Load indicators will flash
.
After a normal POWER+ shutdown the display screen indicates a load of zero amps, the UPS status is
“OK, OFF”; the Static Switch status is “OK, BYP”.
LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)
Figure 64: Main screen after a power shutdown
Figure 65: Main screen after a power shutdown indication
1.
Press twice on the On/Off button on the upper right of the system controller panel.
Wait about 2 minutes for the
POWER+
to start up.
The following screen is displayed:
LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (ON)
L3:__________ 000A, 120V STSW OK (INV)
Status
indications
Figure 66: Main screen at power-up
Observe that UPS OK indication is now ON and the STSW OK now indicates INV.
If the display continues to indicate BYP, check on the Static Switch panel, that the inverter is running.
Содержание PowerPlus RM 100
Страница 27: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 13 Figure 7 Battery cabinet wiring...
Страница 44: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 30...
Страница 81: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 67 Figure 82 Service sub menu...
Страница 174: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 160 Table 21 List of SMS commands...