Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
126
7.
Select
GATEWAY
:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]
1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1
Figure 258: Network menu
8.
Use the arrows keys to set the gateway and press
Ent
:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network > Set GATEWAY]
Set GATEWAY
157.211.000.251
Figure 259: Setting the gateway
9.
Select
MASK
:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]
1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1
Figure 260: Network menu
10. Use the arrows keys to set the mask and press
Ent
:
[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network > Set MASK]
Set MASK
255.255.255.000
Figure 261: Setting the mask