Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
90
5.
Use the arrow keys to set the battery minimum temperature alarm value, press
Ent
, and then
Esc
:
[Main Menu > SETUP > (password) > ALARM SET > Temperature > UNDER TEMPERATURE]
SET OVER TEMPERATURE ALARM VALUE
( 2 – 99) DEGREES
45
Figure 139: Set battery minimum temperature alarm
10.8.4
Setting Battery Integration Alarm
The Alarm Integration Factor determines the number of times that the controller polls and retries to
determine the UPS status before deciding on an error status. Setting the alarm integration factor too low
will cause spurious alarms to be generated; conversely, setting the alarm integration factor too high may
result in an alarm only being raised when it is already too late to take corrective action.
1.
Select
INTEGRAT.
:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 140: Alarm set menu
2.
Use the arrow keys to set the integration factor alarm value—press
Ent
to accept or
Esc
to discard:
[Main Menu > SETUP > (password) > ALARM SET > INTEGRAT.]
SET INTEGRATION FACTOR
(1 – 30)
ENTER = ACCEPT 05 ESC = DISCARD
Figure 141: Set the integration factor alarm
Содержание PowerPlus RM 100
Страница 27: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 13 Figure 7 Battery cabinet wiring...
Страница 44: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 30...
Страница 81: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 67 Figure 82 Service sub menu...
Страница 174: ...Gamatronic Electronic Industries Ltd POWER RM100 3X208 V User Guide 1 3 160 Table 21 List of SMS commands...