Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
88
3.
Use the arrow keys to set
BATEND
and press
Ent
:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATEND]
FLOATING CHARGE SETUP
VOLTAGE SETTING: 170.0V
Figure 130: Set BATEND
4.
Select
BATLOW
:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 131: Battery floating charge alarm setup menu
5.
Use the arrow keys to set
BATLOW
and press
Ent
:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATLOW]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 170.0V
Figure 132: Set BATLOW
6.
Select
BAT-HI
:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 133: Battery floating charge alarm setup menu
7.
Use the arrow keys to set
BAT-HI
, press
Ent
, and then
Esc
:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BAT-HI]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 340.0V
Figure 134: Set BAT-HI