26
G5 User Guide
6.5
Power+ protocol alarms
Table 10: PowerPlus protocol alarms
N
UMBER
N
AME
D
ESCRIPTION
1
UPS modules warning
More than 1 UPS Module is sending an alarm or fault warning
2
One UPS module warning
Single UPS Module is sending an alarm or fault warning
3
More than 1 master
encountered
N.A.
4
Output voltage discrepancy
N.A.
5
Load on bypass
Load is now running on bypass
6
An alarm/s is vibrating
Alarm(s) vibrating (alarm is frequently raised and lowered)
7
Over temperature
Excess temperature
8
No AC output to load
No ac output to load
9
High battery voltage
Excessive battery voltage
10
Not used alarm 10
N.A.
11
End of backup
End of battery backup. Battery is discharged to shutdown limit
12
Low battery voltage
Low battery voltage
13
Static switch warning
Static Switch warning or alarm
14
Emergency Power Off
activated
Emergency Power Off is active
15
Not used alarm 15
N.A.
16
Last battery test fail
Batteries failed last test
17
User 1 input open
User 1 input volt-free contact open (NC)
18
User 2 input open
User 2 input volt-free contact open (NC)
19
User 3 input open
User 3 input volt-free contact open (NC)
20
Input brownout
Momentary input ac voltage failure
21
AC input high
Ac input voltage is too high
22
AC input failure
Ac input failure
23
STSW not responding
Static Switch is not responding
24
Last self test failed
Last controller self-test failed
25
Battery CB is open
Battery circuit breaker is open
26
Suspect fault current
sharing
Possible current sharing fault
27
Suspect a fault output
stage
Possible fault (no current) in 1 or more module output stage
28
UPS shutdown
UPS is shutdown
29
Load current high
Overload
30
UPS or more not
responding
One or more modules not responding
31
Startup time-stamp
Startup time-stamp, indicates controller startup, always present
32
User 4 input open
User 4 input volt-free contact open (NC)