G
AMATRONIC
E
LECTRONIC
I
NDUSTRIES
L
TD
.
Centric Installation Guide, rel. 2.8
69
12.
C
ENTRIC SPECIFICATIONS
Table 8: Technical specifications
CENTRIC:
UPS SYSTEM SPECIFICATIONS
Topology
Modular, double-conversion, VFI, on-line battery
Operation
Continuous
Input
Voltage (V)
3x400 (4 wires + Gnd)
Voltage range (%)
-20 / +15
(360 ~ 460 Vac: full power; 320 ~ 360 Vac: derated 20 %)
Current (A)
3 × 42 per module – no inrush current at startup
Rectifier frequency (Hz)
40 ~ 70
Power walk-in (sec)
1 ~ 30 in 1 sec increments
Power factor correction
>0.99
THDI (%)
<3
Inrush current
None
Output
Rated Power (kVA/kW)
25 ~ 200
Nominal frequency (Hz)
50/60
Frequency tracking range (Hz)
±(0.5, 1, 2, 3, 4), selectable
Frequency tracking slew rate (Hz/sec)
1
Frequency (in free-running mode) (Hz)
50/60 ±0.1 %
Nominal voltage (Vac)
3x400 (4 wires + Gnd)
Static voltage regulation (%)
±1
Regulation for 100 % unbalanced load (%)
±1
Dynamic response to 100 % load step (%)
±2
Overload withstand
Inverter mode
110 % : 10 min, 125 % : 60 s, 150 % : 30 s
Bypass mode
125 % : 10 min, 1000 % : 1 cycle
Waveform
Sinusoidal
THD (%)
Linear load: <2; non-linear load: <6
Load CF (max)
6:1
Power factor
Any
Ac-Ac efficiency (nominal) (%)
Up to 96
Batteries
Dc-link voltage (Vdc)
+/– 405
Quantity
60 × 12 Vdc
Type
Sealed, lead-acid. Lithium-ion batteries also supported.
General
Maximum power dissipation (Po=25 kW)
N*1041 W (N*3552 BTU/h), where N = # modules
Ambient temperature (°C)
-10 to +40 (operating), -20 to +60 (storage)
Relative humidity (%)
95 maximum, non-condensing
Altitude (m)
1500 without derating
Enclosure
IP20
Cooling system
Multi-fan with speed control (forced)
Design & manufacturing standards
Safety
IEC 62040-1
EMC
IEC 62040-2
Design classification
IEC 62040-3
Low magnetic field radiation
EMF as per ICNIRP
Dimensions
UPS model
50 kW
100 kW
200 kW
# of power modules
1
2
2
3
4
4
5
6
7
8
Power output (kW/kVA)
25
50
50
75
100
100
125
150
175
200
Height (mm) (w/o wheels)
665
932
1200
Width (mm)
540
Depth (mm)
757
Weight (kg) w/o batt. box
72.2
92.0
102.4
122.2
142
149.3
169.1
188.9
208.7
228.5
Dimensions (H x W x D, mm) & weight of batt. box for 50 kW system 985 x 540 x 743, 66 kg
All specifications are subject to change without notice.