12
Version 1, 21 August 2019, 12 of 21
10.0
MAINTENANCE
When installed as an AS/NZS 4032.4 application it is a requirement that the commissioning (section 7) and
maintenance procedures (section10) are carried out before use.
10.1 Adjustment of the mix temperature:
1. Turn off both the hot and cold
water supply. Disable mains
power supply from proximity
sensor.
2. Remove top cap, screw and
cover.
3. The setting rings are located either
side of the tap stop, to stop
movement of the tap spindle.
4. Remove both rings and turn tap
spindle till desired temperature
is achieved.
5. Reposition both rings on
either side at the tap stop so
that the tap spindle cannot
move.
6. Refit the cover, the screw and the
top cap.
10.2 Removal and inspection of cartridge
UPPER RING
LOWER RING
Top Cap
Retaining Screw
Cover
Sequential Cartridge
36 mm A/F
(Deep socket required)