Gallagher T20 Reader

  Document Code: 3E3140 

Edition 3, April 2013

Installation Note  

Installation

The Gallagher T20 Reader can be mounted on:

•  a vertical, rectangular 50 mm x 75 mm (2” x 3”) flush box
•  a BS 4662 British Standard square flush box
•  any solid flat surface

The recommended mounting height for the reader is 1.1 m (3.6 ft) from the floor 

level to the centre of the reader device.  However this may vary in some countries 

and you should check local regulations for variations to this height.

Notes:  

•  Installation on metal surfaces, particularly those with a large surface area 

will reduce read range.  The extent to which the range is reduced will depend 

upon the type of metal surface.

•  When mounting on a flush box, the corner screws must be used as well as the 

flush box screws.  Without corner screws the top of the product is vulnerable 

to seperation from the wall.

•  The reader cannot be mounted on a mounting block.

1. 

Ensure the building cable has been run out through the flush box.
If you are not mounting to a flush box, use the reader base as a guide, to drill 

all five holes.  Drill the 13 mm (1/2 inch) diameter centre hole (this is the 

centre hole for which the building cable will exit the mounting surface) and 

the four corner fixing holes.  Ensure the centre hole allows the cable to run 

freely out through the mounting surface, so that the reader facia can clip into 

the base.

Note:  There is no room for the building cable to be scrunched into the reader 

base.  The building cable must remain within the flush box or wall cavity.

2. 

Run the building cable through the reader base.

Note:  If the reader has already been connected to the building cable, you can 

pass the facia through the base.  Great care must be taken to avoid scratching 

the screen and keypad when passing the facia through the base.

3. 

Secure the base to the flush box using the two screws provided.  When 

securing the base to a vertical, rectangular flush box, use the 6-32 UNC screws 

provided.  When securing the base to a BS 4662 British Standard square flush 

box, use the M3.5 screws provided.

4. 

Drill pilot holes for the four corner fixing holes.  Secure the base to the 

mounting surface using the four corner fixing screws provided.  It is important 

the four corner fixing screws are used to ensure the reader is flush with and 

tight against the mounting surface. 
Note:  It is strongly recommended that you use the screws provided.  If an 

alternative screw is used, the head must be no larger nor deeper than that of 

the screw provided.

Содержание T20

Страница 1: ...eads Mifare DESFire EV1 Mifare Plus Mifare Classic and 125 KHz cards The reader sends information to the Gallagher Controller and acts upon information sent from the Gallagher Controller The reader it...

Страница 2: ...o operate over a supply voltage range of 9 16 Vdc measured at the reader terminals The operating current draw is dependent on the supply voltage at the reader For the Mifare reader at 12 Vdc the curre...

Страница 3: ...42 4 x 0 4 mm2 Not twisted pairs 21 AWG 200 m 650 ft 150 m 500 ft The matching of wire sizes to equivalent wire gauges are only approximate Notes Shielded cable may reduce the obtainable cable length...

Страница 4: ...hole for which the building cable will exit the mounting surface and the four corner fixing holes Ensure the centre hole allows the cable to run freely out through the mounting surface so that the rea...

Страница 5: ...ons Positive Red Negative Black Reserved Orange Reserved Green Reserved Brown CDXIV TX White CDXIV RX Blue Cardax IV Reader 7 Fit the facia assembly into the base by clipping the small lip into the to...

Страница 6: ...a piece of gaffer tape Stick the tab to the facia over the Gallagher logo and use it to pull the facia out of the base then remove the tape without leaving a mark Connections The Gallagher T20 Reader...

Страница 7: ...te Cardax IV Reader 2 Gallagher GBUS Universal Reader Interface Gallagher GBUS URI Connect the wires to the sockets as shown in either of the following diagrams RLY 2 COM RLY 2 NO RLY 2 NC DATA 0 DATA...

Страница 8: ...COM NO NO NO NO NC NC NC NC PF1 PE1 P1 0V VIN COMB 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 1 1 2 DETECTOR LED RS485 POWER IN J4 J3 J2 J1 0V 0V 0V 0V VOUT VOUT VOUT VOUT PA4 PA3 PA2 PA1 2 1...

Страница 9: ...PA Positive Red Negative Black Reserved Orange Reserved Green Reserved Brown CDXIV TX White CDXIV RX Blue Cardax IV Reader Positive Red Negative Black Reserved Orange Reserved Green Reserved Brown CDX...

Страница 10: ...utine maintenance Not applicable for this reader Cleaning This reader should only be cleaned with a clean lint free damp cloth Voltage 9 Vdc 16 Vdc Current at 12Vdc 82 mA standby Mifare reader 115 mA...

Страница 11: ...n Note Document Code 3E3140 Edition 3 April 2013 Icons The Gallagher T20 Reader displays the following icons Arming Failed Arming Succeeded Armed Present Card Present Second Card Enter PIN Access Gran...

Страница 12: ...V technician for help Industry Canada This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interfere...

Страница 13: ...ting Dimensions 179 5 mm 7 07 inches 95 7 mm 3 77 inches 6G Screw 60 3 mm 2 37 inches 29 1 mm 1 14 inches 60 3 mm 2 37 inches 83 3 mm 2 78 inches Flush Box Screw Cable Exit 125 card read area Mifare c...

Отзывы: